230 V~

50/60 Hz

230 V~

50/60 Hz

ENGLISH

6

  

The service bracket (rif. 

) allows to freely rotate the screws

 

of the travel-limit device in order to set the configuration

 

as per figure 11.  

Proceed as indicated below:

When the shutter is fully down, the position of the screws of the travel 
limit device, ref. 

 and 

 must be as shown in Fig. 11;

Check if the screw of the closing travel limit device (ref. 

), presses 

on the closing microswitch (ref.

) to engage it (the microswitch 

emits a light “CLICK” when it is engaged).
Make sure that the screw of the opening travel limit device 
(ref. 

) is in contact with the bush (ref.

) on the left side. The 

opening microswitch (ref.

) must not be in contact with the screw 

as shown in Fig. 11.

 

Do not remove the service bracket before completion 
of the electric installation of the motor and before 
being ready for the first automatic movement of the 
shutter.

1.

2.

3.

During installation, the positions of the mechanical travel limit devices 
may alter, thus compromising the subsequent automatic procedure for 
determining the stop positions of the shutter. For this reason, the position 
of the travel limit devices must be checked and, if necessary, adjusted 
before starting the application.

 

 

Screw of opening travel limit device 

 

 

Screw of closing travel limit device 

 

 

Rotation constraint lever

 

 

Opening microswitch 

 

 

Closing microswitch 

 

 

Reference bush

 

 

Service bracket

4  TRAVEL LIMIT UNIT

5 ELECTRICAL 

CONNECTIONS

The gearmotors for shutters R180 and R280 can be commanded by 
direct power, supplied by a 230 VAC selector, or by control boards 
200 BT and 200 MPS.

  

To install two R180/280 units on the same winding 
shaft, please refer to chapter 8 on page 8 BEFORE 
performing the following electrical connections.

The gearmotor is supplied with a pre-wired power cable with a length of 
4 meters. Fit this cable in the hole drilled on the winding shaft (as shown 
in chapter 1.2 “MECHANICAL PREPARATIONS”), making it come out from 
the side of the winding shaft in which you intend to install the movement 
commands or the electrical pull-boxes.

 

The electronic command received from a 
button-board/selector at 230 Vac, can only be used 
indoors.

5.1  BUTTON-BOARD OR SELECTOR 230 Vac

The 200BT control board makes it possible to connect two push-buttons 
commanded on low voltage (24 Vdc) with dead man logic.
An electronic interlock system prevents simultaneous powering of the 
electric motor in the two operating directions.

5.2  COMMANDS WITH 200BT CONTROL BOARD 

Neutral

Neutral

Open

Close

Open

Close

Fig. 12

Fig. 11

In the R180 and R280 applications the travel limit devices are integrated 
and, therefore, the dedicated connections on the 200BT board must be 
short circuited.
In Figure 13 jumper connect terminals 2 and 3 to terminal 1.
For further information on the connection and operation of the 200BT 
control board, consult the instructions supplied with the board.

The 200MPS control board makes it possible to manage more control 
functions and logics.
To make the connections, consult the instructions supplied with the 
board.

5.3  COMMANDS WITH 200MPS CONTROL BOARD 

Fig. 13

Make the connections shown below according to the type of 
command used.

BL

UE or GREY

BL

UE or GREY

Summary of Contents for R180

Page 1: ...UTOMATED SYSTEM 4 3 1 PRELIMINARY CHECKS 4 3 2 INSTALLATION DIMENSIONS 4 3 3 INSTALLING THE OPERATOR 4 4 TRAVEL LIMIT UNIT 6 5 ELECTRICAL CONNECTIONS 6 5 1 BUTTON BOARD OR SELECTOR 230 Vac 6 5 2 COMMA...

Page 2: ...ds EN 12453 and EN 12445 For non EU countries to obtain an adequate level of safety the Standards mentioned above must be observed in addition to national legal regulations 11 Before attempting any jo...

Page 3: ...nt temperature 40 C 55 C Shutter Shaft Diameter 60 48 42 mm 60 48 42 mm Winding Flange Diameter 200 220 mm 200 220 mm Maximum Shutter Height 8 m 8 m Maximum Shutter Width 4 5 m 4 5 m Operator Weight 8...

Page 4: ...he shutter shaft removing deposits of dust grease and chips To install two R180 or R280 operators on a shutter having a width of over 4 5 meters please refer to chapter 8 on page 8 Procedure for defin...

Page 5: ...on the winding shaft Insert in the hole you have just drilled the securing screw in Fig 7 ref tightening it to rest on the washer and self locking nut 5 6 If in chapter 1 2 you have measured a windin...

Page 6: ...power supplied by a 230 VAC selector or by control boards 200 BT and 200 MPS To install two R180 280 units on the same winding shaft please refer to chapter 8 on page 8 BEFORE performing the followin...

Page 7: ...ake the shutter into its fully closed position to obtain full access to the travel limit unit 1 As shown in Figure 14 incline downward and keep inclined the rotation constraint lever ref to enable rel...

Page 8: ...1 Close the cover of both travel limit units and reposition the service brackets Continue the installation performing only for the MASTER operator the instructions given from chapter 5 on page 6 There...

Reviews: