7.4 J1 - INPUTS
Manual and automatic controls can be connected to input J1
to manage the 2 AIRSLIDE speeds.
A three-position switch connected between pin2 (V1) and pin3 (V2)
and pin6 (GND) allows speeds V1 (low) and
speed V2 (high) to be managed.
Using pin 4 (I1) and pin5 (I2) it is possible to manage speeds V1 and V2
automatically.
7.5 J2 INTERCOM
(with E1SL firmware version 3.2 or later)
It is possible to manage the AIRSLIDE speeds via the
Intercom connection between board E1AS and board E1SL of the
automatic door
27
.
Intercom communication occurs by selecting ID
addresses on the E1AS board.
The possible addresses are as follows:
E1AS
E1SL
SW4
(SDK EVO)
9
1
10
2
11
3
12
4
13
5
14
6
15
7
The SW4 ID addresses from 0 to 8 on the E1AS board are not active
■
Description
The E1AS board is able to communicate with other E1AS units via an
Intercom network connection and programmed via the
E1SL board of the automatic door and the programming unit SDK EVO.
This allows the various functions (Programming menu/Intercom/
Function) to be performed:
!
Every network connected E1SL should be programmed for the same
Intercom mode.
■
Connection
The network connection of the units uses three wires in a cascade
between connectors J18 of the E1SL boards and J2 of the E1AS boards.
The sequence in which the units are wired is unimportant, but it is
essential that a CASCADE connection is used.
■
Addressing
A unique node ID must be assigned to each E1AS present in the net-
work (Programming menu/Intercom/MasterSlave_nr) .
!
Do not assign the same Node ID to more than one unit in the network.
■
Registration
After having wired up and assigned an address to each unit, registra-
tion must be carried out (Programming/Intercom/Node registration)
only on the Master E1SL that has been assigned Node ID=1.