3. INSPECTION AND PREPARATION
3.2 ARRANGEMENT OF ELECTRICAL CABLES
!
Before performing any operation on the system, disconnect the
power supply.
The electrical system must be compliant with the regulations in
force in the Country of installation (EN60335-2-80 : 2003 + A1 : 2004
+ A2 : 2009)
The power mains of the automation must be fitted with a multi-pole
power switch with a switch-contact gap of at least 3 mm. It is ad-
visable to use a 6A circuit breaker with a multi-pole power switch.
Ensure there is a residual current device with a 0.03 A threshold
upstream of the system.
!
Ensure the earthing system is constructed in a workmanlike manner
and connect the structure’s metal parts to it.
If it is necessary to control board E1AS remotely, provide additional
cables to maintain a continuous earth .
Lay the electrical cables for connecting the accessories and
the electrical power supply
4
.
Protect cables by means of suitable ducting.
!
Place control accessories within the automation’s visual range. These
devices must always be accessible, even with the door open.
Comply with the following heights from the ground:
- control accessories = minimum 150 cm
- emergency buttons = max 120 cm
3.1 PRELIMINARY INSPECTION
!
Prior to installation, check soundness of the load bearing masonry
structure and door. Perform any required work to assure:
- solidity, stability and absence of any risk of detachment or collapse
of the masonry structure, fixed door frame and automation
- level flooring, without any friction/hindrance to smooth leaf sliding
- absence of sharp edges (cutting hazard)
- absence of protruding parts (hooking/entrainment hazard)