14.3 CONFIGURATION OF J22 OUTPUTS
O1 and O2 specifications:
O1 Open Collector output with Max load 100mA to be connected
between 01 and V.
(Can be configured from SDK EVO)
O2 relay contact with Max load 2A to be connected between O2
and O2.
(Can be configured from board and SDK EVO)
The OUT1 and OUT2 output signals may be configured as listed below:
Output configured as DISABLED
-
keeps the output always off.
Output configured as GONG
-
on and off at 1 sec. intervals when the closing safety devices
are busy.
Output configured as ERROR
-
the output is on when there is any active error.
Output configured as BATTERY
-
the output is on when operation is with battery i.e. there has
been a power outage.
Output configured as ACTIVE EMERGENCY
-
the output is on when an emergency is on.
Output configured as TEST
-
the output is on to command test execution (FAIL SAFE) on inputs
I1- I4 configured as closing safety and on which the TEST option
has been activated before a closing motion.
Output configured as DOOR NOT CLOSED
-
the output is on when the door is in NOT CLOSED status.
Output configured as DOOR OPEN
-
the output is on when the door is in open status.
Output configured as DOOR IN MOTION
-
the output is on when the door is moving (opening or closing).
Output configured as LIGHT
-
the output is on for a programmable time in NIGHT-TIME opera-
tion from leaf opening.
Output configured as INTRUSION
-
the output is on when an intrusion is in progress (i.e. when the
encoder detects an unexpected movement of the door from the
closed position over 1 cm.)
Output configured as Safety in Closing.
-
activates the output when at least one Safety in Closing is On.
Output configured as Safety in Closing or Safety in Opening
-
activates the output when at least one Safety in Closing or Safety
in Opening is On.
the output is on depending on how it has been programmed:
- normally open means the output contact closes when the output
is on
- normally closed means that the output contact opens when the
output is on.
14.4 OBSTACLE DETECTION
Obstacle in closing (default 2)
Any acknowledgement of an obstacle in CLOSING determines inver-
sion of the leaves and increase in the number count of consecutive
obstacles in closing. The force and time parameters with which the
motor forces on the obstacle can be selected.
Error 24 is generated when the programmed number of obstacles in
CLOSING is reached.
The number of consecutive obstacles in closing is reset to zero:
-
with RESET command
-
upon reaching the CLOSED position
Obstacle in closing (default 1)
Any acknowledgement of an obstacle in OPENING determines a
stop of the motion and after 10 s a new attempt of opening. Error 24
and then error 31 are generated when the programmed number of
obstacles in OPENING is reached.
The number of consecutive obstacles in opening is reset to zero:
-
with RESET command
-
upon reaching the OPEN position
-
An obstacle detected during opening in NIGHT-TIME function
stops the leaves and after the night-time pause time set they
close again.
(safeties in closing and inputs not active)
14.5 ANTI-INTRUSION AND PULL&GO
The anti-intrusion is active when the door is manually moved from
the CLOSED position.
It is hindered during an attempt to open to return to the closed posi-
tion and signal 63 is activated.
The anti-intrusion is NOT active in NIGHT-TIME function with battery
operation.
The PULL&GO is active when the door is manually moved from the
CLOSED position to facilitate opening via activation of the motor.
The anti-intrusion is NOT active in PULL&GO function.
C1=16
C1=16
or
CI=17
CI=17
NO
NO
(NO input)
(programmable from board or
from SDK EVO )
CI
CI
=
nC
nC
(NC input)
(programmable only
from SDK EVO )