A1400 AIR RDT
70
532119 04 - Rev. C
Tr
ansla
tion of the original instruc
tions
ENGLISH
INTERNAL OPEN input
-
manages 3 types of input of this kind:
-
NO or NC CONTACT (can be selected for I1, I2, I3,I4, I and E ter-
minals)
-
IN CURRENT (can be selected only for E- and E+ or I- and I+
terminals)
-
IN FREQUENCY (can be selected only for E and I terminals)
-
With active contact of an input configured in this way the leaves
must open and remain in the open status for as long as the input
is active.
-
With inactive contact the pause time elapses and the leaves
close again.
-
the ENERGY SAVING mode can be activated on this input.
-
the TOTAL or PARTIAL function can be selected on this input.
-
this function is NOT activated in NIGHT-TIME mode except the
interval of time for switching to NIGHT-TIME FUNCTION.
-
activation of this input lights up the OPEN green LED on the
board.
OPENING EMERGENCY WITHOUT MEMORY AND WITH MEMORY input
-
manages this type of input E1 E2 inputs as NO or NC contact.
-
once the E1 input has been configured, also E2 input is automati-
cally configured in the same way.
-
in the event in which the 2 E1 and E2 inputs take on different
levels, ERROR 17 activates.
-
With active contact of this input, the leaves open and remain
open for as long as the input is active
-
With inactive contact the pause time elapses and the leaves
close again.
-
the input configured as EMERGENCY in OPENING acts differ-
ently depending on whether is it programmed with or without
memory :
1. without memory, input deactivated the leaves close again.
2. with memory, input still deactivated the leaves remain open until
the RESET command is given.
-
opening is always TOTAL.
-
this function is active in NIGHT-TIME function.
-
this function is NOT active in MANUAL function.
-
activation of this input lights up the EMERG green LED on the
board.
PARTIAL / TOTAL FUNCTION input
PARTIAL / TOTAL FUNCTION input
-
this type of input can only be activated on I1, I2, I3 and I4 termi-
nals as NO or NC contact.
-
With contact active this input overrides a PARTIAL operating
mode.
-
With contact inactive this input overrides a TOTAL operating
mode.
-
in an input configured in this way with SDK EVO and LKEVO, the
functions can be modified, except PARTIAL / TOTAL.
NIGHT-TIME FUNCTION input
NIGHT-TIME FUNCTION input
-
this type of input can only be activated on I1 and I2 or I3 and I4
inputs as NO or NC contact.
-
once the I1 input has been configured, also I2 input is automati-
cally configured in the same way.
-
once the I3 input has been configured, also I4 input is automati-
cally configured in the same way.
88
-
in the event in which the 2 inputs take on different levels, ERROR
17 is triggered.
-
With active contact of both inputs configured in this way over-
rides a MANUAL operating mode.
-
With inactive contact of both inputs configured in this way the
NIGHT-TIME mode is exited.
-
in an input configured in this way with SDK EVO and LKEVO the
functions can be modified, except NIGHT-TIME.
MANUAL FUNCTION input
MANUAL FUNCTION input
-
this type of input can only be activated on I1 and I2 or I3 and I4
inputs as NO or NC contact.
-
once the I1 input has been configured, also I2 input is automati-
cally configured in the same way.
-
once the I3 input has been configured, also I4 input is automati-
cally configured in the same way.
88
-
in the event in which the 2 inputs take on different levels, ERROR
17 activates.
-
With active contact of both inputs configured in this way over-
rides a MANUAL operating mode if the contact is maintained. (It
CANNOT be modified with SDKEVO).
-
With inactive contact of both inputs configured in this way the
MANUAL mode is exited.
-
in an input configured in this way with SDK EVO and LKEVO the
functions can be modified, except MANUAL.
TIMER input
TIMER input
-
With active contact the TIMER functionality is activated.
-
With inactive contact the TIMER functionality is disabled.