background image

10 

Connect the Main Power 

WARNING!

 Turn off the main power before 

you make any electrical connections. 

 

The installer is responsible for providing a dedicated 20 
Amp circuit breaker and for making sure that all 
electrical wiring and connections conform to all 
applicable electrical codes. 
 
By now, the conduit from your power source should be 
stubbed up beneath the operator as discussed earlier in 
the operator mounting section and shown in Figure 2. 
 
The 885 Operator requires 115 VAC.  The 115 volt 
power should run through the 2” knockout on the right 
side of the operator and be terminated in the junction box 
(single gang handy box) mounted slightly above the 
knockout, see Figure 6.  Remove the blank cover and run 
the power wires in through the open fitting on the left 
side of the box.  Connect the 115-volt line to the black 
wire (or the black wire labeled “1”).  Connect the neutral 
to the white wire (or the black wire labeled “2”).  
Connect the ground wire to the yellow wire with the 
green stripe.  Reinstall the cover on the junction box. 
 
 

 

Figure 6. The right side of the 885 Operator 

 

Power Switch and Receptacle 

On the top of the 885 Operator (next to the control panel) 
there is a main power disconnect switch and a 115-volt 
receptacle.  The switch controls power to the entire 
operator, including the receptacle.  The receptacle 
provides power for keypads, telephone entry systems, 
and other devices that require the use of a plug-in 
transformer. 

Connect Accessory Devices 

WARNING!

 Turn off the main power before 

you make any electrical connections. 

 

Plug-in Loop Detectors 

The 885 CAT provides terminals for plug-in Free Exit 
and Safety loop detectors.  When plugging the detectors 
in, be sure that the component side of the detector faces 
the display on the 885 CAT.  If the installation does not 
require the use of one or both detectors, simply leave the 
appropriate terminal empty. 
 
The terminal labeled “EXIT LOOP” or “J1” accepts a 
detector to serve as a free exit.  Plug the detector in and 
connect the loop leads to terminals 11 and 12.  If you are 
using more than one exit loop, connect the loops in series 
across terminals 11 and 12.  See Figures 7 and 8. 
 
The terminal labeled “SAFETY LOOP” or “J2” accepts 
a detector to serve as a safety.  Plug the detector in and 
connect the loop leads to terminals 9 and 10.  If you are 
using more than one safety loop, connect the loops in 
series across terminals 9 and 10.  See Figures 7 and 8.  
To activate the Safety Loop Detector you must install a 
jumper across terminals 7 and 8, and enable Safety 2 by 
choosing Y on the S2 function of the programming.  See 
the 

Programming

 section on page 13. 

 
For more detailed instructions on the loop detectors, 
consult the Diablo Controls instruction sheet included 
with your operator. 
 

Plug-in Radio Receiver 

The 885 CAT provides a terminal for the FAAC plug-in 
radio receiver.  Simply match the DIPswitches on the 
receiver with those on the transmitters and plug it in to 
the terminal labeled “DECODER” or “J6”.  The receiver 
can only be plugged in one way. 
 

Slave Card 

There is an optional card that enables you to run two 
operators in a master/ slave configuration.  It also has six 
relays to give you contact closures at different positions. 
See the 

Optional Equipment

 section on page 16. 

Summary of Contents for 885

Page 1: ...1...

Page 2: ...ay from the road to eliminate the potential of traffic getting backed up This distance is affected by the size of the gate how often it is used and how fast the gate operates 2 The operator you choose...

Page 3: ...quipment 3 If a gate system component malfunctions turn off the main power before making any attempt to repair it 4 Do not attempt to impede the movement of the gate You may injure yourself as a resul...

Page 4: ...ect Accessory Devices 10 Plug in Loop Detectors 10 Plug in Radio Receiver 10 Slave Card 10 Activation Devices 12 Safety Devices 12 Stop Devices 12 Accessory Power 12 LED Indicators 13 Programming 13 T...

Page 5: ...When you receive your 885 Operator inspect the shipping box for physical damage Then inspect the operator once you have removed it from the box Notify the carrier immediately if you note any damage b...

Page 6: ...s of the operator Remove the operator and use a masonry bit to drill holes the appropriate depth for your concrete anchors Use concrete anchors that are at least 3 long Once the holes are drilled and...

Page 7: ...7 Figure 2 The footprint of the 885 Operator top view...

Page 8: ...at this procedure in the closed position by setting the closed limit 6 12 short as well to be sure that the gate does not travel too far once power is applied Figure 3 The 885 Limit Assemblies Manual...

Page 9: ...the assembly to the right 3 Note the position of the solenoid return springs above and below the solenoid pin and remove them for safekeeping 4 Remove the two clip in nuts that were used to mount the...

Page 10: ...ectrical connections Plug in Loop Detectors The 885 CAT provides terminals for plug in Free Exit and Safety loop detectors When plugging the detectors in be sure that the component side of the detecto...

Page 11: ...Terminal F1 1 6A Accessory DL6 Encoder J6 Radio Receiver F2 12 5A Main Power DL7 Close Limit J7 Battery Back Up DL8 Stop J8 Limit Switches Switches Buttons DL9 Safety 1 J9 Transformer Primary SW1 DL10...

Page 12: ...ate must have normally closed N C contacts Connect the normally closed N C to terminal 3 Safety 1 and the common COM to terminal 5 Common Multiple devices should be connected in series The way that th...

Page 13: ...y programming changes Pause time selects the pause time before automatic close from 0 seconds to 4 minutes A logic only Time is adjusted in one second increments from 0 to 60 seconds After 60 seconds...

Page 14: ...tware of the 885 CAT Y Be sure to choose this setting n Do not use Will cause the control panel not to function Slave selects master or slave operator in a master slave configuration Y slave operator...

Page 15: ...it searches for the limit switches Once it is complete the operator will run at full speed Continue to cycle the gate and test all input devices Be sure that all safety devices are functioning proper...

Page 16: ...must be connected to the master unit 4 Program the following function on the master operator Stand Alone AL Y Slave SL N 5 Program the following function on the slave operator Stand Alone AL Y Slave S...

Page 17: ...nel and it is ready for an open signal You can open the gate one time and then the back up will shut down until AC power is restored When running on battery power the photobeams will function normally...

Page 18: ...to the control panel area Leave enough slack for the four connectors to be plugged into the batteries before the batteries have been slid into the tray Do not install the batteries yet 10 Reach in the...

Page 19: ...rming any maintenance or repairs The manufacturer recommends that only qualified personnel check and maintain the equipment Problem When an activation signal is sent the open light DL3 comes on but th...

Page 20: ...e the power switch on the top of the operator is on 3 Check the F1 and F2 fuses on the control panel with an ohm meter or continuity tester 4 Make sure that the transformer is connected properly to th...

Page 21: ...e or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceeding those set...

Reviews: