FAAC 885 Instructions For The Use Download Page 8

Preliminary Limit Adjustment 

Before moving the gate manually with the chain 
attached, you must back the limit adjusters off (spin them 
toward the center of the adjusting rod)(See Figure 3). 
Doing so will insure that you will not bottom them out 
on the end of the threaded rod as you move the gate.  To 
do this, lift the wire retainer while spinning the adjuster. 

 

Once the limits are backed off, you can move the gate by 
hand, watching to make sure that the limit adjusters do 
not reach the end of the threaded rod as you move open 
and closed. 

 

Because the main power has not yet been applied, you 
should be able to move the gate by hand.  Roll the gate to 
the full open and closed positions and make any 
adjustments to the chain mounting that are necessary. 

 

Once the chain is properly aligned, move the gate to the 
open position and then the closed position to perform a 
preliminary limit adjustment.  As you move the gate 
open, notice that the limit adjusters are moving toward 
one of the limit switches.  This is your open limit switch.  
Lift the wire retainer and spin the closest limit adjuster 
toward the open limit switch.  Temporarily set it so that 
it engages the switch before the gate is all the way open 
(6”-12” short of the open position).  Be sure that it 
triggers the switch early by slowly moving the gate by 
hand. 

 

Repeat this procedure in the closed position by setting 
the closed limit 6”-12” short as well to be sure that the 
gate does not travel too far once power is applied. 

 

 

Figure 3. The 885 Limit Assemblies 

Manual Release 

The 885 Operator features a lockable, manual slide lever 
that allows you to unlock the gate at any time.  As 
indicated by the label on the operator cover, the gate is 
engaged when the lever is down and disengaged when 
the lever is up. 
 

 

Figure 4.  The 885 Operator’s Manual Release 

Lever and Lock Solenoid (shown in fail-safe and 

fail-secure positions) 

 

The control panel of the 885 operator features a selection 
when programming, that allows you to choose whether 
the gate will be locked or not in the event of a power 
failure.  The SO (solenoid, discussed on page 14) 
function of the operator gives you two choices: 

Fail-safe mode: Gate can be moved manually 
when power fails. 

n

 

Fail-secure mode: In the event of a power 
failure, you must use the manual release 
mechanism for manual operation of the gate. 

In addition to the programming choice, the solenoid itself 
must be mounted in the proper position for the operator 
to function correctly.  The solenoid is installed at the 
factory in the fail-safe position (shown in figures 4 & 5).  
This is the factory recommended position if you are not 
using the optional battery backup system (see 

Optional 

Equipment

 on page 15).  Unless you re-mount the 

solenoid in the fail-secure position you must choose Y 
(fail-safe) on the SO function setting.

Limit Adjusters 

Fail-Safe

Fail-Secure 

Summary of Contents for 885

Page 1: ...1...

Page 2: ...ay from the road to eliminate the potential of traffic getting backed up This distance is affected by the size of the gate how often it is used and how fast the gate operates 2 The operator you choose...

Page 3: ...quipment 3 If a gate system component malfunctions turn off the main power before making any attempt to repair it 4 Do not attempt to impede the movement of the gate You may injure yourself as a resul...

Page 4: ...ect Accessory Devices 10 Plug in Loop Detectors 10 Plug in Radio Receiver 10 Slave Card 10 Activation Devices 12 Safety Devices 12 Stop Devices 12 Accessory Power 12 LED Indicators 13 Programming 13 T...

Page 5: ...When you receive your 885 Operator inspect the shipping box for physical damage Then inspect the operator once you have removed it from the box Notify the carrier immediately if you note any damage b...

Page 6: ...s of the operator Remove the operator and use a masonry bit to drill holes the appropriate depth for your concrete anchors Use concrete anchors that are at least 3 long Once the holes are drilled and...

Page 7: ...7 Figure 2 The footprint of the 885 Operator top view...

Page 8: ...at this procedure in the closed position by setting the closed limit 6 12 short as well to be sure that the gate does not travel too far once power is applied Figure 3 The 885 Limit Assemblies Manual...

Page 9: ...the assembly to the right 3 Note the position of the solenoid return springs above and below the solenoid pin and remove them for safekeeping 4 Remove the two clip in nuts that were used to mount the...

Page 10: ...ectrical connections Plug in Loop Detectors The 885 CAT provides terminals for plug in Free Exit and Safety loop detectors When plugging the detectors in be sure that the component side of the detecto...

Page 11: ...Terminal F1 1 6A Accessory DL6 Encoder J6 Radio Receiver F2 12 5A Main Power DL7 Close Limit J7 Battery Back Up DL8 Stop J8 Limit Switches Switches Buttons DL9 Safety 1 J9 Transformer Primary SW1 DL10...

Page 12: ...ate must have normally closed N C contacts Connect the normally closed N C to terminal 3 Safety 1 and the common COM to terminal 5 Common Multiple devices should be connected in series The way that th...

Page 13: ...y programming changes Pause time selects the pause time before automatic close from 0 seconds to 4 minutes A logic only Time is adjusted in one second increments from 0 to 60 seconds After 60 seconds...

Page 14: ...tware of the 885 CAT Y Be sure to choose this setting n Do not use Will cause the control panel not to function Slave selects master or slave operator in a master slave configuration Y slave operator...

Page 15: ...it searches for the limit switches Once it is complete the operator will run at full speed Continue to cycle the gate and test all input devices Be sure that all safety devices are functioning proper...

Page 16: ...must be connected to the master unit 4 Program the following function on the master operator Stand Alone AL Y Slave SL N 5 Program the following function on the slave operator Stand Alone AL Y Slave S...

Page 17: ...nel and it is ready for an open signal You can open the gate one time and then the back up will shut down until AC power is restored When running on battery power the photobeams will function normally...

Page 18: ...to the control panel area Leave enough slack for the four connectors to be plugged into the batteries before the batteries have been slid into the tray Do not install the batteries yet 10 Reach in the...

Page 19: ...rming any maintenance or repairs The manufacturer recommends that only qualified personnel check and maintain the equipment Problem When an activation signal is sent the open light DL3 comes on but th...

Page 20: ...e the power switch on the top of the operator is on 3 Check the F1 and F2 fuses on the control panel with an ohm meter or continuity tester 4 Make sure that the transformer is connected properly to th...

Page 21: ...e or accident or has not been operated in accordance with FAAC International Inc s or FAAC S p A s instructions or has been operated under conditions more severe than or otherwise exceeding those set...

Reviews: