Outputs
Each ezeio
™
supports up to 40 outputs. Each output has two possible states:
on or off.
Outputs can be controlled by events or states.
Event controlling outputs
Event triggers include alarm actions, timer actions, schedule actions, email
and text commands, or manual toggling of the buttons on the
ezecontrol.com
Status page.
When triggered, the ezeio
™
will send a single command to the selected
output. This method will control the relay state until the next command is
received.
State controlling outputs
Relays can be directly controlled by conditions. By checking the
Use only
conditions
box, event commands and manual controls will be disabled.
The ezeio
™
will continuously force the state of the output as long as the
conditions selected are true (see Conditions, page 48).
The settings for each output are:
Output name
A user defined name for the output.
Output location
This defines the hardware where the
output is located.
One-shot coil msg
This setting only applies to modbus
connected output devices. If checked,
the set command will only be sent when
the output status changes. The default
(unchecked) is that the modbus set command is repeated every 20 seconds.
Use only conditions
If this box is checked, the conditions will continuously be re-evaluated, and
the output set accordingly. That means that any other attempts to control the
output will be overruled.
Leaving this box unchecked means that the condition settings are not used.
The output state is set by manual commands, alarm actions, remote
commands or script.
For more details on conditions, see Conditions
page 48.
Page 49 of 121