Thermostats / Thermostat schedules
The ezeio
™
can communicate with up to 10 thermostats connected to the
Modbus network. The thermostats are controlled by thermostat schedules
that are defined under the
Thermostats
menu.
Every ezeio
™
supports up to four (4) thermostat schedules, and each
thermostat schedule can control up to four (4) physical thermostats, with a
total maximum of 10 thermostats per ezeio
™
.
To associate a thermostat to a thermostat schedule, first define the
thermostat schedule, then find the thermostat under the
Device
menu,
and select the appropriate thermostat schedule.
All thermostats that are associated with schedules will be listed on the status
page automatically, where the current status of the thermostat will be shown.
Conditions for using alternate settings
Associated thermostats will be switched to alternate mode if the conditions
selected evaluate to “true”.
Other settings / Stir
The stir feature monitors the activity of each thermostat, and will ensure that
the fan runs with the set interval as a minimum. If the thermostat
automatically uses the fan for heating or cooling, the stir timer is reset to
avoid unnecessary fan activity.
Stir holdoff
sets the maximum number of minutes the fan is allowed to be
off.
Stir time
sets the number of minutes the fan should run if there is no other
activity.
Page 51 of 121