background image

7

ENGLISH

InstallIng Inserts

When installing inserts, access must be prevented to the internal parts of the appliance and it must not be possible to access live parts during 

extraction operations.

Any wiring, for example the power cable or room probe, must be positioned so as not to be damaged during movement of the insert and must 

not come into contact with hot parts. If a cavity made of combustible material is installed, we recommend taking all the safety precautions 

indicated by the installation standards.

VentIlatIOn anD aeratIOn OF InstallatIOn rOOMs

In case of non-airtight heater and/or installation, the ventilation must respect the minimum area indicated below (considering the highest value 
among those provided):

appliance categories

Reference standard

Percentage of the 

net opening section with respect to the 

appliance fumes outlet section

Minimum net opening value of the 

ventilation duct

Pellet stoves

UNI EN 14785

-

80 cm²

Boilers

UNI EN 303-5

50%

100 cm²

InstallatIOn

general

The flue gas exhaust and hydraulic connections must be carried out by qualified personnel who must issue installation conformity 

documentation compliant with national standards.

the installer must provide the owner or person acting for him, according to the legislation in force, with the declaration of conformity, 

supplied with:

1) the use and maintenance manual of the appliance and of the system components (such as for example, the smoke ducts, chimney, etc.);

2) photocopy or photograph of the chimney plaque;

3) system booklet (where applicable).

The installer must ask to be issued with a receipt stating that the documentation has been provided, and must keep it with a copy of the technical 

documentation relating to the installation.

For installation in a condominium, prior approval from the condominium's administrator must be requested.

Where required, check the exhaust gas emissions after installation. Should a sampling point be installed, it must be airtight.

COMPatIBIlItY 

Do not install in rooms with a fire hazard. It is also forbidden to install it in living areas with the following characteristics:

1.  where there are liquid fuel appliances with continuous or discontinuous operation that draw the combustion air into the room in which they 

are installed.

2.  where there are type B gas appliances intended for heating, with or without domestic hot water production and in adjacent and communicating 

rooms.

3.  where the depression measured in situ between the external and internal environment is greater than 4 Pa.

N.B.: Watertight appliances can also be installed in the cases indicated in points 1, 2 and 3 of this paragraph.

InstallatIOns In BathrOOMs, BeDrOOMs anD stuDIO Flats

Installation in bathrooms, bedrooms and studio flats is only allowed for sealed or closed hearth appliances with ducted combustion air taken 

from the outside.

floor protection

POsItIOnIng anD saFetY DIstanCes 

The support surfaces and/or points must have a suitable capacity to bear the overall weight 
of the appliance, accessories and coverings. If the floor is made of a combustible material, 
we recommend using a non-combustible material to protect the front part from any burnt 
material which might fall during routine cleaning operations. The generator must be level 
to function properly.  The side walls, the rear walls and the floor support surface should be 
made of non-combustible material.

One must also bear in mind all laws and national, 

regional, provincial and town council regulations in force 

in the country in which the appliance has been installed, 

as well as the instructions contained in this manual.

Air inlet

Under any condition, including in the presence of extractor hoods and/or of controlled forced ventilation systems, the pressure difference 

between the generator installation rooms and the outside must always be equal to or less than 4 Pa.

MInIMuM DIstanCes (Pellet stOVes)

Installation next to flammable or heat-sensitive materials is permitted 

only if the special 

safety distances specified on the label at the beginning of the manual (pag.2) are 

observed

. If the materials are not flammable, you must keep a side and rear distance of at 

least 100 mm (without the inserts). For products equipped with rear spacers, wall-mounting 
installation is permitted exclusively for the rear side.

PreParatIOns FOr MaIntenanCe

To carry out extraordinary maintenance operations on the product, it may be necessary to move it away from the adjacent walls. This must be 

done by a technician authorised to disconnect the combustion product evacuation ducts and then reconnect them. For heaters connected to the 

hydraulic system, the connection between the system itself and the product must be made in such a way that, when an authorised technician is 

about to carry out extraordinary maintenance operations, it is possible to move the heater at least 1 metre away from the adjacent walls.

Summary of Contents for GUENDA IDRO

Page 1: ...MADE IN ITALY design production GUENDA IDRO 004280684 rev 000 ENGLISH UK THERMO PRODUCTS USER MANUAL...

Page 2: ...2 ENGLISH APPLY TECHNICAL DATA LABEL...

Page 3: ...thermostat operation with STAND BY active 22 Additional thermostat operation with STAND BY deactivated 22 ADDITIONAL THERMOSTAT INSTALLATION 22 VENTILATION 23 EASY SETUP 23 CHRONO 24 ENABLING DISABLIN...

Page 4: ...ance has been installed as well as the instructions contained in this manual The use of the appliance must comply with all local regional national and European regulations The Manufacturer cannot be h...

Page 5: ...IF IT IS DISCONNECTED FROMTHE MAINS It is advised to position the power supply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible afte...

Page 6: ...clean the majolicas it is recommended to use a soft dry cloth If a detergent or liquid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICA...

Page 7: ...mestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances can als...

Page 8: ...always be insulated The smoke ducts must have at least one airtight inlet for flue gas sampling All the sections of the flue gas duct must be accessible to inspection Inspection openings must be prov...

Page 9: ...houses because it does not take air in from within the house combustion air To ensure the stove remains hermetically sealed the connection pipe for the combustion air must be directly connected to th...

Page 10: ...and inspection of correct functioning must be carried out perfectly in full compliance with Standards in force national regional and municipal as well as these instructions For Italy installation mus...

Page 11: ...This is to prevent unexpected power increases The flue fitting can be mounted between the boiler and the flue only after this inspection An inspection of the connections with pre existing flues is re...

Page 12: ...safety drain T2 Boiler flow output T3 Boiler return input Combustive air input Room air outlet Pellet hopper Heat exchanger scrapers Door handle Fumes exhaust Not used fuse Power supply 230v On Off He...

Page 13: ...veying motor and therefore operation of the heat generator The system must be bled several times to eliminate the air and loaded when the pressure is too low It is not an anomaly but normal phenomenon...

Page 14: ...ion means that you have 60 to close the hatch door and the pellet lid If this is not the case during ignition the stove will go to DEPRESSION ALARM mode while during normal operation the stove will go...

Page 15: ...LITY PELLETS OR ANY OTHER MATERIAL DAMAGES THE FUNCTIONS OF THE GENERATOR AND CAN VOID THE WARRANTY AND THE ANNEXED RESPONSIBILITY OF THE MANUFACTURER Pellet tank During the operation of the stove the...

Page 16: ...On off stove hold for 3 seconds 9 Degrees Celsius Fahrenheit 4 Set power 10 Press the button once to enable or disable the chrono 5 Set switch off delay The button allows to set the switch off delay F...

Page 17: ...Handle the remote control with care When it is not being used place it on the special base supplied The remote control must not be left in a place where it is exposed to direct sunlight or near a sour...

Page 18: ...external additional thermostat Closed contact the contact of the external additional thermostat is closed Open contact the contact of the external additional thermostat is open WI FI BT STBY OK ON STA...

Page 19: ...ed to be connected to a hydraulic system it must be complete and fully functional and in compliance with the instructions given in the product manual and with the relevant regulations in force The pel...

Page 20: ...and confirm by pressing key 6 Select the language using keys 4 or 5 Press key 6 to confirm and key 1 to scroll back through the menus until the initial page DEGREES This menu allows you to set the un...

Page 21: ...s of the room temperature probe integrated in the product see the chapter VENTILATION on the following pages BLOW During the working phase the stove has an internal timer which after a pre set period...

Page 22: ...the stove and relative factory setting restrictions If the stove is in H OFF water temperature reached any additional contact or thermostat request will be ignored Additional thermostat operation with...

Page 23: ...e keys 4 5 to set the range Press key 6 to confirm and key 1 to scroll back through the menus until the initial page N B IF THESE ADJUSTMENTS DO NOT SOLVE THE PROBLEM OF PELLET DEPOSITS IN THE BURN PO...

Page 24: ...s and confirm by pressing key 6 Confirm ENABLING by pressing 6 Use keys 4 5 to enable ON or disable OFF Press key 6 to confirm and key 1 to scroll back through the menus until the initial page J If we...

Page 25: ...t 3 1 02 00 23 00 08 00 16 30 t 72 68 2 1 25 ENGLISH Time slot 1 Start 02 00 Stop 23 00 Power 3 SET H2O 72 C Time slot 2 Start 08 00 Stop 16 30 Power 1 SET H2O 68 C Stove operation TIME SLOT SET POWE...

Page 26: ...ressing key 3 until STAND BY appears and confirm by pressing key 6 Use keys 4 5 to enable ON disable OFF Press 1 several times to confirm and exit the menu FIRST LOAD This function allows the auger to...

Page 27: ...key 6 Use keys 4 5 to enable ON disable OFF Press key 1 several times to confirm and exit the menu EASY CONTROL The function allows for two values to be set OFF disabled factory default ON enabled Act...

Page 28: ...pressed the message KEYS LOCKED will appear To lock the keypad press keys 1 and 5 simultaneously until the following message appears KEYS LOCKED To unlock the keypad press keys 1 and 5 simultaneously...

Page 29: ...e the warranty CLEANING THE CERAMIC GLASS Never use abrasive or chemically aggressive detergents for cleaning The ceramic glass must be cleaned when the glass is completely cold To clean the ceramic g...

Page 30: ...ng it at the back A Clean the combustion chamber and the bottom of the burn pot completely using a suitable vacuum cleaner Refit the ash conveyor by performing the same operation in reverse Always mak...

Page 31: ...s to be vacuumed and cleaned If there are horizontal sections the residue must be removed to prevent it from obstructing the flow of fumes SHUT DOWN END OF SEASON At the end of each season before turn...

Page 32: ...and door replace and apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning E Check air intake pipe a...

Page 33: ...only if the generator has been in an OFF state for at least 96 hours the pump is activated for the time pre set by the manufacturer in order to prevent it from blocking AUTO BLOW The automatic blow is...

Page 34: ...ER CONTROL ALARM Abnormal pellet feeding Contact after sales centre AUGER BLOCKED Abnormal operation of pellet motor Contact after sales centre TRAPDOOR BLOCKED The automatic cleaning of the burn pot...

Page 35: ...kindly asked to separate this equipment and or batteries or accumulators included from other types of waste and to arrange for disposal by the municipal waste service It is possible to ask your local...

Page 36: ...0445 865911 39 0445 865912 info extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufactu...

Reviews: