Make sure that measures have been taken to avoid unintended triggering and transmission
of alarms before applying test gas. Activate the alarm bypass in service mode at your ExTox
Control Unit, deactivate automatically triggering protection measures or inform the respon-
sible maintenance personnel. The measures corresponding to your application have to be
determined and the person in charge for maintenance has to be familiar with all details.
8.4
System Check
The system check additionally comprises the triggering of switching functions; check of sys-
tem parameters and of indication and recording facilities.
9
Technical Data and Declaration of Conformity
The Data Sheet of the control unit contains all technical data (
)
DB).
Data sheets and Declaration of Conformity are added to the documentation separately.