ES2030 SV
Display and modification of the basic settings
25
16. ‘Additional program’ output
An additional relay can be controlled during the regeneration of a filter. This can
be used to initiate washing programs or switch on supply or dosage pumps. In the
following steps the switch on point is set before, during or after regeneration, and
the time the relay stays switched on is determined.
In each case, the switch on point is the start of a new regeneration phase. But if
phase ‘0’ is entered as the switch on point the additional program runs before the
actual regeneration program.
Or if the letter ‘E’ (for end) is selected as the switch on point, the additional
program is running after the end of the regeneration.
Switch on point
Switch on time
Values from 1 to 999 minutes can be entered for the switch on time of the
additional program.
Switchover of service valve
If phase ‘0’ was entered as switch on point at program step 16.1, it has to be
decided whether the open service valve of the filter in service is to be shut
immediately when the additional program is switched on (Y/N) or it is only closed
on completion of the additional program time (Y/N).
In the case of two filter systems in alternate service, it is determined whether to
switch immediately to the standby filter (Y/N) or if this only happens on
completion of the additional program time (Y/N).
NOTE: When ‘SV changeoverY/N’ the programmed setting ‘Stop in
service’(program step 4.1 –SP) is activated.
17. ‘Regeneration’ output
If the ‘regeneration’ function is selected, the relevant additional relay is activated
for the full time of the regeneration.
NOTE: No program data are entered for this function.
Step no.: 16.1
Start phase 2
Step no.: 16.2
Time ’On’ 20m
Step no.: 16.3
SV changeoverY/N
15.3
18.1-21.1
Phase
16.1
minutes
16.2
Yes No