EWS ES2030 SV Manual Download Page 10

ES2030 SV 

Messages 

 

Messages 

 
During service and during the regeneration of 
the system, various signals are given 
depending on the type of controller and its 
programming. 
These signals can be signalled with the built-in 
buzzer and displayed in the LCD display. If the 
extension card IF2030 is installed an additional 
relay can be selected as warning relay (step 
15).  
 
 
 
Press the key OUT1 or OUT2 to clear the 
buzzer and any activated warning relay. The 
LCD display is only cleared when the warning 
signal is no longer active. 
 

Capacity exceeded 

 
 
 
 
 
This display can only appear with a double 
filter system. 
While one of the filters is regeneration, the 
other was also called on to regenerate. The 
warning in the LCD display is cleared when 
this filter starts regeneration. 
 
Possible causes where activated by the water 
meter : 
   Incorrect setting of capacity, supply water  
   hardness or of the water meter itself. 
   Overloading of the system e.g. by filling a  
   large container. 
 
Possible causes where activated externally by 
a water analysis device : 
   Saturation of a system newly put into use,  
   caused by the negative ion effect. 
   Solution : fit a flushing valve or circulation 
   pump. Reduce the sensitivity of the analysis  
   Device. 
 
Other possible causes : 
   Poor regeneration of the filter due e.g. to     
   regeneration medium not being present or  
   being incorrectly primed. 
 
NOTE: In two-filter systems, after a flow 
dependent regeneration activation the 
regeneration of the second filter will follow 
immediately the current regeneration ends. 
However in the case of external activation of 
the regeneration, e.g. by a water analysis 
device, the regeneration does not follow, as it 
can be assumed that the hardness warning 

occurred as a result of a standstill hardening of 
the standby filter. The second filter is only 
regenerated if the relevant start signal is still 
present at the end of the current regeneration 
or if it reset. 
In the case of ion exchangers with a salt 
release valve, if no brine has yet formed for the 
second filter, stop the regeneration by 
switching off the unit. 
 
 

Power failure 

 
 
 
 
 
No data are lost if there is a power failure. 
When power is restored the control panel will 
return to the same setting with the same 
values.  
NOTE: If the system is at the regeneration 
setting when power is lost, the filter may 
become over saturated again if the water 
pressure continues during this time and it is 
washed by supply water over a period of 
hours. 
If so, stop the regeneration and then re-start. 
 

Refill regeneration medium 

 
 
 
 
 
Refill regeneration medium. 
NOTE: An imminent regeneration will not be 
carried out unless either regeneration medium 
is again available or the “start regeneration” 
key with the symbol     is pressed. 
In the case of alternately operating two filter 
systems, the unit switches over to the standby 
filter. 
 

Delayed regeneration 

 
 
 
 
 
The required regeneration will not start until the 
time shown in the LCD display. However the 
regeneration can be started immediately by 
pressing the “start regeneration” key (     ). 
This display is only shown if activation of 
“delayed regeneration” was selected in step 19 
or 21. 

  S T A T U S 
Instal.exceeded 

  S T A T U S 
Supply failure 

OUT

1

OUT

2

  S T A T U S 
Refill RegMedium 

  S T A T U S 
Prohibited Reg. 

Summary of Contents for ES2030 SV

Page 1: ...Control for ion exchangers and filter systems Instruction manual Software version 3 00 ES2030 SV...

Page 2: ...m run 5 Filter capacity 5 Water delivery 6 Input states 6 Output states 6 Service number 6 Software version 6 Programmed inputs 6 Programmed outputs 6 Last regeneration 6 Regeneration ratio 6 Messages...

Page 3: ...ation times 16 6 Delayed regeneration 17 Starting on real time clock 18 7 Interval start of regeneration 18 8 Minimum regeneration distance 19 9 Definition of input functions 20 10 Water meter input 2...

Page 4: ...angers A regeneration can be initiated 1 by manual switch 2 by remote switch water hardness monitor conductivity meter manual switch etc 3 by pre selected amount pulse water meter required 4 after set...

Page 5: ...Start regeneration 12 Information 17 Output 2 LED 3 Regeneration filter 1 8 Supply water 13 Programming 18 Output 1 LED 4 Regeneration filter 2 9 Time 14 LCD display 5 Main fuse 10 Output 1 15 Input 1...

Page 6: ...eration or The time of the next regeneration if a delayed regeneration has been initiated see program step 6 or The number of hours until the next regeneration see program step 7 or Alternating with t...

Page 7: ...F 4 199 E 2 99 mg l CaCO3 40 1999 gpg 2 99 no unit 0 01 9999 99 m3 0 02 mmol l 0 10 D 0 13 E 0 18 F 1 79ppm 0 11gpg USA 0 13gpg UK The calculation of the soft water quantity with altered values is ca...

Page 8: ...played MinRg 4 If a minimum regeneration distance was selected during programming at step 8 the time interval in hours is shown Otherwise MinRg is displayed Additional program Bottom left the starting...

Page 9: ...uts The programmed functions of input IN1 and IN2 if the IF2030 card is fitted are displayed Programming the outputs The programmed functions of output OUT1 and OUT2 are displayed NOTE This display is...

Page 10: ...s However in the case of external activation of the regeneration e g by a water analysis device the regeneration does not follow as it can be assumed that the hardness warning occurred as a result of...

Page 11: ...automatically at the end of set minimum regeneration distance or whether the next regeneration has to be started manually NOTE The message in the LCD display is not cleared until regeneration is start...

Page 12: ...regeneration interval is reset Special functions These functions should only be used by a professional water treatment specialist as their improper use may lead to malfunctions Filter change over with...

Page 13: ...eration without initialisation For maintenance purposes it is sometimes necessary to check the regeneration program without initialising the pulse counter or recalculating the filter capacity Simultan...

Page 14: ...programming changes the key has to be held down for 4 seconds before the basic values are released for change The LCD display first shows the following message After 4 seconds this changes to NOTE Con...

Page 15: ...llel to alternate Valve control for alternate service and parallel service can be entered at 4 1 For this the controller must first be programmed for alternate service 1 3 at Yes and then for parallel...

Page 16: ...In alternating service or parallel service one filter continues to supply treated water while the other is regenerating If it too becomes saturated because the amounts drawn off are too large the mes...

Page 17: ...nnector OUT2 ATTENTION This program step can only be selected if the controller is fitted with the IF2030 expansion card In this step you van select the outputs OUT1 V7 and or OUT2 V8 for magnetic val...

Page 18: ...t program step 3 1 the service position the stop position in service and the stop position during regeneration are also programmed display SV SP or HO phase The stop position in service can be activat...

Page 19: ...r each of the periods according to the number of regeneration phases No times are entered for the service and stop positions Enter period number and the required time in the range from 1 to 990 minute...

Page 20: ...with a 2 filter system operating in parallel with sequential regeneration It can be determined whether the service valve or both service valves should stay open until the regeneration time entered Ma...

Page 21: ...ns can also be initiated at fixed intervals This periodic initiation is selected where a water meter is not necessary because the amounts of water drawn off are constant It is also used to prevent mic...

Page 22: ...lly before the set time has elapsed by water meter time interval or analysis device the appropriate message is shown on the LCD display and the built in buzzer sounds if programmed at program step 21...

Page 23: ...ter SP stop service ST start regeneration CH chemicals shortage HO stop regeneration Input function IN2 Place the cursor under the required input function NOTE This program step can only be selected i...

Page 24: ...unt The pulse rate of the water meter can be entered as a pulse interval in litres pulse or as a pulse count in pulses litre Water meters without reducing gears also known as turbines emit a high numb...

Page 25: ...is always entered regardless of whether the system is made up of one or more filters FILTER SYSTEMS If no supply water hardness was selected at step 10 3 the capacity of one filter can be entered in...

Page 26: ...r is resent at the end of the current regeneration NOTE No program data are entered for this function 13 Chemicals shortage input This input can be used to monitor the chemicals supply to ion exchange...

Page 27: ...ng NOTE The functions flow pulse and flushing can only be selected if the system Is fitted with a water meter NOTE This step will not be selected if the relay is programmed for valve function in step...

Page 28: ...the switch on time of the additional program Switchover of service valve If phase 0 was entered as switch on point at program step 16 1 it has to be decided whether the open service valve of the filte...

Page 29: ...dditional relay 1 or 2 selected not selected If more than one signal is selected the relevant relay functions as a combined warning relay M Minimum regeneration distance Note Only where minimum regene...

Page 30: ...in two filters systems with water meter S Stop during service Note Only where an input with Stop function is selected C Chemicals shortage Note Only where an input for monitoring the chemicals is sel...

Page 31: ...ES2030 SV Examples of systems 28 Examples of systems Double sand filter with individual valves V2 V3 V1 Input 1 WM V5 V6 V4 1 3a 3b 2 3b 2 3a 1 F2 F1...

Page 32: ...nder voltage to Connector V1 terminals 5 and 6 Connector V2 terminals 8 and 9 Connector V4 terminals 13 and 14 Connector V5 terminals 16 and 17 Example 2 Connecting a servo motor to Connector V1 termi...

Page 33: ...T1 terminals 3 and 28 bridge from 4 to 27 Connector OUT2 terminals 3 and 31 bridge from 4 to 30 Example 5 Connection to a magnetic valve active when voltage not applied on potential free relay output...

Page 34: ...ES2030 SV Wiring diagram 31...

Page 35: ...ing connection work Make electrical connections Observe local regulations Connect supply voltage and ground to the terminals shown in the wiring diagram Make sure that the ground connection is faultle...

Page 36: ...otal continuous current 4 A 115 24V 230 24V Total continuous current 2 A Dry contact Max load capacity 250V 4A Inputs Load capacity 9V 8 mA Protection class IP65 Ambient temperature 0 40 C Weight Appr...

Page 37: ...e ES2030SV Manufacturer EWS Equipment for Water treatment Systems International B V Australi laan 12 NL 5232 BB s Hertogenbosch The Netherlands Product environment This product is intended for use in...

Page 38: ...to the carrier e Removal or installation of the product f Any other cause which does not relate to a product defect g Cartons equipment enclosures cables or accessories uses in conjunction with the pr...

Page 39: ...ally prohibited by applicable law EWS shall not be liable for 1 Damage to other property caused by defects in the EWS product damages based upon inconvenience loss of use of the product loss of time c...

Reviews: