pro CONTROL BASIC Manual
page 18
5.6
Parameter
5.6.1 Zone parameter
Step
Operation
Description
1.
Select the zone(s) as described in 5.1
2.
Press key to change to the parameterization level
3.
Select parameter.
Each time the arrow keys are pressed, the parameter is
incremented or decremented.
4.
Use the buttons to set the value of the selected parameter
to the desired value.
Note! Password entry required before parameterization
(default "22"). Set the current password with the keys and
confirm. The parameter can then be changed
The display flashes. This means that the value has not yet
been accepted.
5.
Confirm the entry.
The display stops flashing.
6.
Press the Home button to return to the overall display of all
zones.
pro CONTROL BASIC Manual
page 19
5.6.2 System parameter
Step
Operation
Description
1.
… 2
s
Press and hold for 2s.
The display changes to the system parameter level.
This level contains system information that cannot be
changed:
System Information
However system parameters and system functions can be
changed. The representation is made as
or
:
System Parameter
System Function
2.
Select system parameters.
3.
Set the value of the selected parameter to the desired
value using the arrow keys.
Note! Password entry required before parameterization
(default "22"). To do this, set the current password with the
keys and confirm. The parameter can then be changed
The display flashes, indicating that the value has not yet
been accepted.
Example: System parameter
with value 500
4.
Confirm the entry.
The display stops flashing.
5.
Press the Home button to return to the overall display of all
zones.
19
pro CONTROL BASIC hot runner controllers – Operating manual