14
WT.050.810.040.DE.IM.0817
Description
DEPOLOX
®
5 E flow cell
3.
DEPOLOX
®
5 E flow cell is available in both a non-pressurized
and a pressurized version. The two versions differ in the number
of sensors that can be installed and in the design of the sample
water outlet. The non-pressurized version is characterized by a
free sample water outlet. With the pressurized version, the sample
water is returned into the system’s circuit.
The for sensors required for the measurement tasks (optional) and
the LED glow stick are inserted or screwed into the mounting hole
in the cell body cover.
The maintenance-free flow control valve is the main hydraulic part
of DEPOLOX
®
5 E flow cell. It has the task of keeping the sample
water flow constant, irrespective of fluctuations in operating pres-
sures.
The multi-sensor monitors the correct flow and records the tem-
perature of the sample water. The metallic sensor housing guaran-
tees good sample water earthing. The continuous
hydromechanical cleaning of the electrode of the three-electrode
measuring cell effectively prevents natural contamination of the
electrode surfaces and ensures long-term stable chlorine mea-
surement.
DFMe electronics module converts the analog sensor signals for
digital transmission to 700 P electronics module or 700 M electron-
ics module. If a membrane sensor for total chlorine TC2 CAN or
TC2-S CAN (optional) is used, this is connected directly to DFMe
electronics module or routed through the CAN connection on con-
ductivity module SiDiSens (optional) to DFMe electronics module.
The conductivity sensor (optional) is connected to DFMe electron-
ics module through conductivity module SiDiSens.
3.2
Versions
The DEPOLOX
®
5 E flow cell (module type D01) can be comined
with 700 P electronics module (module type E01) or 700 M elec-
tronics module (module type E01). The following versions are
available:
•
Pool Management System DEPOLOX
®
5 E 700 P
•
Measuring and control unit DEPOLOX
®
5 E 700 M
Summary of Contents for WALLACE & TIERNAN DEPOLOX 5 E
Page 1: ...WALLACE TIERNAN DEPOLOX 5 E FLOW CELL INSTRUCTION MANUAL...
Page 8: ...8 WT 050 810 040 DE IM 0817 Introduction DEPOLOX 5 E flow cell 1...
Page 82: ...82 WT 050 810 040 DE IM 0817 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 83: ...DEPOLOX 5 E flow cell Declarations and certificates 7 83 7 2 Certificate of CSA...
Page 84: ...84 WT 050 810 040 DE IM 0817 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 85: ...DEPOLOX 5 E flow cell Declarations and certificates 7 85...
Page 86: ...86 WT 050 810 040 DE IM 0817 Declarations and certificates DEPOLOX 5 E flow cell 7...
Page 90: ...90 WT 050 810 040 DE IM 0817 Index DEPOLOX 5 E flow cell 8...