TCP/IP Network Access Controller
37
4.8.3
Enter Alarm Setting Menu
In the “System Setting” main menu, select “Alarm Setting” menu item and press “#” to
enter the submenu. The submenu of the “Alarm Setting” has “AlarmIN Setting” and “Alarm
Action Setting” submenu items for setting physical alarm input and alarm output time of
alarm events, respectively.
4.8.4
AlarmIN Setting
Select the “AlarmIN Setting” menu item and press “#” to enter its interface. Because the
controller only has one alarm input circuit, the system will display the alarm type of the
current alarm input. The default alarm type of the alarm input port of the system is a fire
alarm. The user can scroll to the alarm type to be set and press the numerical key “5” to
select. Press “#” to save the current setting and enter the next step.
4.8.4.1
Fire Alarm Setting
There are two fire alarm input modes: Normally Opened and Normally Closed. Normally
Opened means the circuit disconnects in the normal condition (i.e. without input) and
connects with activated inputs. Normally Closed is the opposite: the circuit connects in the
normal condition (i.e. without input) and disconnects with activated inputs.
Door Action on
Alarming
:
Close
[
#
]
to toggle
Door Action on
Alarming
:
Open
[
#
]
to toggle
Input mode
:
*NO
NC
Alarm Port
:
1 2
N N
AlarmIN Type
:
2
Others
*Fire
Cancel
Next
AlarmIN Type:
Others
*Fire
Cancel
Next
AlarmIN Type:
* Other
Fire
Cancel
Next
AlarmIN Setting
Alarm Action Setting