EVCO S.p.A.
Vcolor 818
| Installer manual ver. 1.1 | Code 144VC818E114
page 67 of 94
d1
0
4
- - - -
1
type of defrosting
0 = electrical (the compressor will be switched off during
defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)
1 = hot gas (the compressor will be switched on during
defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)
2 = air (the compressor will be switched off during
defrosting and the defrosting output will be
activated; the evaporator fan will be switched on,
independently from the conditions of the door, i.e.
independently from the door micro switch input
status)
3 = air with door open (the compressor will be switched
off during defrosting and the defrosting output will
be activated; the evaporator fan will be switched on,
on condition that the door is open, i.e. that is on
condition that the door micro switch is active and
that the parameter i0 is set at values different to 0)
4 = reserved
d2
-99
99
°C/°F (1)
2
defrosting end temperature (evaporator temperature); see
also parameter d3
d3
0
99
min
30
if parameter P4 is set at 0, duration of defrosting
if parameter P4 is s et at 1, maximum duration of
defrosting; see also parameter d2
0 = defrosting will never be activated
d4
0
1
- - - -
0
defrosting on start-up of blast chilling and deep freezing
1 = yes
d5
0
99
min
30
defrosting delay on start-up of storing
0 = defrosting will be started on expiry of the time
established with parameter d0
d7
0
15
min
2
dripping duration (the compressor and the evaporator fan
remain off during dripping and the defrosting output will be
deactivated)
d15
0
99
min
0
minimum duration of compressor switch-on on activation of
defrosting so these can be activated (only if parameter d1 is
set at 1) (8)