EVCO S.p.A.
EVF 300 series | Installer manual ver. 1.3 | Code 144F300E134
Page 50 of 62
Erd
device settings upload not completed successfully alarm
solutions:
-
to restore the factory settings
main consequences:
-
all outputs will be switched off
ESt
device settings download not completed successfully alarm
solutions:
-
press and release the key
main consequences:
- no
consequence
When the cause of the alarm disappears, the device restores normal operation, except for the following alarms:
-
the use temperature alarm (code “
Ht
”), which requires a key to be pressed and released
-
the power supply cut-off alarm (code “
PF
”), which requires a key to be pressed and released
-
the device settings download not completed successfully alarm power supply cut-off alarm (code “
ESt
”), which requires a
key to be pressed and released
-
the firmware alarm of the original settings not coinciding with that of the destination settings(code “
CEr
”), which requires
the device power supply to be cut-off
‐
the device settings upload not completed successfully alarm power supply cut-off alarm (code “
Erd
”), which requires
factory settings to be restored.