The following table illustrates the meaning of the device configuration parameters.
The indication “1 ING.” indicates “operating with an analogue input” (chamber probe, i.e. with management of the power distributed at
the top and that distributed at the floor independently from each other; the data given in this column is significant only if the CFG
parameter is set at 0). The indication “2 ING.” indicates “operating with two analogue inputs” (top probe and floor probe, i.e. with
management of the top and floor temperature independently from each other; the data given in this column is only significant if the
CFG parameter is set at 1).
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
WORKING SET-POINT
SP
r1
r2
°C/°F (1)
150
not dis.
working set-point; see also r0
SP1
r1
r2
°C/°F (1)
not dis.
150
top set-point; see also r0
SP2
r7
r8
°C/°F (1)
not dis.
150
floor set-point; see also r6
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
POWER SUPPLIED
Po1 0 100 % 50
not
dis.
power distributed at the top (percentage of the time c1);
see also c0
Po2 0 100 % 50
not
dis.
power distributed at the floor (percentage of the time
c1); see also c0
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
STEAM INJECTION
tOn 0 250 s
5 5
if t0 = 0, minimum switch-on duration of the steam
injector
if t0 = 1, duration of steam injector switch-on; see also
tOF and nCY
tOF 0 250 s
15 15
if t0 = 0, not significant
if t0 = 1, duration of steam injector switch-off; see also
tOn and nCY
nCY
0
99
- - -
0
0
if t0 = 0, not significant
if t0 = 1, number of steam injections in cyclical mode;
see also tOn and tOF
0 = until steam injection in cyclic mode will be
deactivated
PARAM.
MIN.
MAX.
U.M.
INP. 1
INP. 2
TYPE OF OPERATION