3.2
Charger positioning (with Auxiliary power cabinet – APC)
As there are some limitations (including cables length), we recommend the following installation for
the charger in relation to a parking space of 2500 mm width:
A:
Distance to the wall
à
Minimum: 600 mm to do not compromise
the access to the rear socket type E or F as
well as to the Auxiliary power cabinet (APC).
B:
Depth of the charger
à
648 mm
C:
Distance between charger and parking
place as marked on the ground
à
Minimum: 500 mm to allow free access to
emergency stop and the HMI
à
Maximum: 800 mm limited by the length of
the vehicle charging cables
D:
Width of the charger
à
920 mm
E & F:
Distance to the parking place
à
Minimum: 550 mm not to hinder the user
when handling the connector.
à
Maximum: 930 mm, limited by the length of
the vehicle charging cables.
(A + B + C) minimum = 1748 mm
Notes:
- It is recommended, so as to avoid
overheating, install it under a shelter or
shaded-area in order to protect from direct
sunlight.
- If installed indoors, the room should be
ventilated by a permanent air exchange
system. The ventilation rate of the charger
can reach 1200 m
3
/h.