Page 19/34
4.2
Electrical connection for charger with storage
Follow all the instructions shown in the previous point “4.1 Electrical connection for charger without
storage” but taking in account next values:
-
A head switch capable of handling at least 80 A to electrically isolate the charger in case of
maintenance.
-
A tetra polar circuit breaker (MCCB), curve D, 80 A, suitable for 36 kVA equipment.
-
A Residual current device (RCD) capable of handling at least the maximum current of the
above-mentioned circuit breaker with a sensitivity of 300 mA; type A, HI, S.
-
36 kW model: 60 A per phase with power factor > 0.98.
4.3
Passage of the input cables
We recommend the use of a flexible multicore 3P+N+T cable or independents flexible cables for
easy installation (either copper or aluminium). A rigid cable can be used, but at the expense of
comfort of the installer.
Be aware about the specific countries rules, there might be some differences in the conductor
material and the kind of cable coating.
It is advisable to adjust the length of the cables to terminal blocks in order to have the least amount
of cable inside the terminal (while retaining some flexibility).
To access the passage of the input cables and their connection to the terminal (see APPENDIX 1),
please remove various covers (see point 3.3.4) from the charger (no need to remove the rear cover)
taking care to remove the ground wires if necessary (do not forget to put them back when
reassembling).
The entrance of the cables (green circle) is accessible on the front side
Feeding cables
Summary of Contents for Troniq
Page 1: ...D000782AA6 EVBox Troniq Installation Manual ...
Page 27: ...Page 27 34 8 APPENDIX 3 DIMENSIONS Charger dimensions without Auxiliary power cabinet APC ...
Page 28: ...Page 28 34 Charger dimensions with Auxiliary power cabinet APC ...
Page 29: ...Page 29 34 9 APPENDIX 4 CONNECTION TERMINALS DETAILS POWER AND COMMUNICATION ...