Special Considerations for Installations Requiring Compliance with UL Standards
Motor Overload Protection
An external motor overload protective device must be provided by the installer.
OR
Motor overload protection is provided in the controller by means of the thermal device in the motor winding. This
protection cannot be evaluated by UL hence it is the responsibility of the installer and/or the local inspector to
determine whether the overload protection is in compliance with the National Electrical Code or Local Code
requirements.
Branch Circuit/Short Circuit Protection Requirements
Model 584S Type 4 Series
UL Listed (JDDZ) non-renewable cartridge fuses or UL listed (JDRX) renewable cartridge fuses, rated 300Vac or
600Vac as appropriate (depending on the rated input voltage of the drive), must be installed upstream of the drive.
For fuse current ratings, see Chapter 1 “Electrical Ratings - Power Circuit”.
Model 584S Type 5 and 6 Series
UL Recognized Component (JFHR2) semiconductor fuses must be installed upstream of the drive. For fuse current
ratings, see Chapter 1 “Electrical Ratings - Power Circuit”. Refer to Table 1.2 below for recommended
semiconductor fuse manufacturer and model numbers.
Fuse Current Rating
Bussmann Model No.
40A
50A
63A
100A
125A
170M3808
170M3809
170M3810
170M3812
170M3813
Table 1.2 Bussmann International Fuses (Rated 660Vac)
Model 584S Type 7 Series
These devices are provided with solid state short circuit (output) protection. Branch circuit protection should be
provided as specified in the National Electrical Code, NEC/NFPA-70.
Short Circuit Ratings
Model 584S Type 4, 5, 6 Series.
Suitable for use on a circuit capable of delivering not more than 5000 RMS Symmetrical Amperes, 240/460V
maximum.
Model 584S Type 7 Series
Suitable for use on a circuit capable of delivering not more than (the value shown in Table 1.3 or Table 1.4) RMS
Symmetrical Amperes, (the value of rated voltage shown in Table 1.3 or Table 1.4) V maximum.
Output Rating
kW
Rated Voltage
V
Short Circuit Rating RMS
Symmetrical Amperes
22 - 37
45 - 75
208 - 240
380 - 460
5,000
10,000
Table 1.3: Constant Torque (Industrial) Ratings
Output Rating
kW
Rated Voltage
V
Short Circuit Rating RMS
Symmetrical Amperes
30 - 37
45
55 - 90
208 - 240
208 - 240
380 - 460
5,000
10,000
10,000
Table 1.4: Quadratic Torque (HVAC) Ratings
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - [email protected]
Summary of Contents for 584S
Page 122: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Page 173: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Page 174: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Page 175: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...