Chapter 7 - The European Directives and the 'CE' Mark
584S Frequency Inverter
7-5
Port
Phenomenon
Test
Standard
Level
Acceptance
Criterion
Generic
Standard
Enclosure
Port
ESD
RF Field
IEC 801-2
IEC 801-3
4 kV CD, 8 kV AD
10 V/m, 1 kHz AM
self recovery
no change
EN50082-1
(1992)
Power
Ports
Fast Transient
Burst, Surge
IEC 801-4,
IEC 801-5
2 kV
1 kV (P-P), 2 kV (P-E)
self recovery
self recovery
Draft
prEN50082-2
(1992)
Signal &
Control
Fast Transient Burst
IEC 801-4
2 kV
self recovery
Power
Interfaces
Fast Transient Burst
IEC 801-4
2 kV
self recovery
The EMC filters for 584S/620 drive modules may be flash tested in circuit up to DC 2850 V for 1 min Ensure all
other equipment that may be damaged by such flash testing has been suitably isolated/removed/short circuited as
applicable. Due to the internal capacitors between phase and earth, the DC voltage should be wound up slowly, to
prevent excessive earth current. For similar reasons AC flash testing cannot be performed due to the excessive earth
leakage current. Repeated flash testing is not recommended as it may degrade the insulation.
EMC RESPONSIBILITY OF MANUFACTURERS/SUPPLIERS/INSTALLERS
For end users of 584S/620 drive modules, a correctly installed power drive system (PDS) created from the supplied
584S/620 will be compliant with the generic emission standards EN50081-1(1992) & EN50081-2(1994) and for
immunity EN50082-1(1992) & prEN50082-2(1992) as previously indicated. Manufacturers/suppliers/installers of
relevant apparatus may use this compliance as a basis for their own justification of overall compliance with the EMC
Directive.
If it is the responsibility of the manufacturer/supplier/installer to establish EMC conformity and to 'CE' mark. There
are three methods of demonstrating conformity:
1)
Self certification to a relevant standard
2)
Third party testing to a relevant standard
3)
Writing a technical construction file stating the technical rationale as to why the relevant apparatus is
compliant. An EMC "competent body" must then assess this and issue a technical report or certificate to
demonstrate compliance.
Upon demonstrating EMC compliance an EC-Declaration of Conformity for the apparatus or machinxe may be
issued and a
'CE'
mark applied.
Professional end users with EMC expertise who are using drive modules and cubicle systems defined as
components who supply, place on the market or install the relevant apparatus must take responsibility for
demonstrating EMC conformance and applying the 'CE' mark and issuing an EC Declaration of Conformity.
Eurotherm Guide
More information is available in a separate Eurotherm Guide entitled “Short Form Overview of European Directives
for Variable Speed Drives and Applications” part number HA389770 available from your local Eurotherm Drives
office.
This manual was downloaded on www.sdsdrives.com
+44 (0)117 938 1800 - [email protected]
Summary of Contents for 584S
Page 122: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Page 173: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Page 174: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...
Page 175: ...This manual was downloaded on www sdsdrives com 44 0 117 938 1800 info sdsdrives com ...