Chapter 8 - Appendices
8 - 50
584S Frequency Inverter
Formula 2
The second response time formula, formula 2, is given below:
Tr
RAMPTIME
d
SRAMP
=
×
×
−
%
%
%
%
%
100
200
200
This can be simplified as follows:
Tr
RAMPTIME
A
B
=
× ×
The factors A and B are given for varying values of
S RAMP %
and
d%
in the tables below:
S RAMP %
A
d%
B
0
1
0
0
10
1.05
10
0.1
20
1.11
20
0.2
30
1.18
30
0.3
40
1.25
40
0.4
50
1.33
50
0.5
60
1.43
60
0.6
70
1.54
70
0.7
80
1.67
80
0.8
90
1.82
90
0.9
100
2
100
1.0