ROOM VOLUME for VENT FREE
7
G Series
Linear Hearth Burner
European
Home
.com
The following formula can be used to determine the maximum heater rating (per the definition of unconfined space) that is al-
lowed in your space:
Maximum BTU/Hr. =
x 1000
Example A: Consider two connecting rooms with an open area between, with the following dimensions: L1 = 151/2 ft., L2 = 12 ft., W
= 12 ft., H = 8 ft.
x
1000
=
52,800
BTU/Hr.
Example B: If there were a door between the two rooms the calculation would be based only on the room with the heater.
x 1000 = 29,760 BTU/Hr.
Will my space support a G Series Linear Hearth Burner?
Maximum BTU/hr. my space will support (use formula above)
a) __________________
BTU/hr. of European Home
G Series Linear Hearth Burner
b) ____37,500________
If the answer to a) is
greater
than b) then your space
will
support the installation of the
G Series Linear Hearth Burner
; if a) is
less
than b) then your space
will not
support an
G Series Linear Hearth Burner
.
(L1 + L2)ft. x (W)ft. x (H)ft.
50
(151/2 + 12)ft. x (12)ft. x (8)ft.
50
(151/2)ft. x (12)ft. x (8)ft.
50
This appliance is for installation in a solid-fuel burning fireplace or UL 127 factory-
built fireplace or in a listed ventless firebox enclosure.
Exception: DO NOT install this appliance in a factory-built fireplace that includes
instructions stating that it has not been tested or should not be used with
unvented gas logs.
W
ARNING