13.11. Submodule errors
Err
or code
Err
or designation
Meaning
Err
or category
Err
or behavior
Tr
oubleshooting/
acknowledgment
LED displays
Submodule
SLOT RED
SLOT GREEN
Incorrect
submodule
Submodule type
detected does not
correspond to the
submodule type
saved
Incorrect
submodule
Submodule will be ignored; no
effect on overall system
Replace submodule, modify system
topology or restart system
3x
Submodule
missing
Submodule
missing, even
though a
submodule has
been taught-in for
the slot
Submodule
missing
Missing submodule will be
ignored; no effect on overall
system
Install submodule or modify system
topology
1x
Submodule
rotated by 180°
Submodule is
installed rotated
by 180°
Submodule
rotated by 180°
Submodule will be ignored; no
effect on overall system
Rotate submodule by 180°
2x
Internal
submodule error
Internal device
error. Submodule
is no longer
functional.
Internal
submodule error
Submodule will be ignored; no
effect on overall system
Replace submodule
0xA0
Error in the
safety equipment
(can be reset
automatically)
E.g.: discrepancy
error (emergency
stop, enabling
switch, key-
operated
rotary switch,
acknowledgment
pushbutton)
Safety error in
submodule
Latching
For submodules to which an external
device is connected (e.g. enabling switch):
check correct function of the external
device.
For errors in the submodule: replace faulty
submodule and send to the manufacturer.
1Hz
13.12. PROFINET errors
Err
or code
Err
or designation
Meaning
Err
or category
Err
or behavior
Tr
oubleshooting
Corr
esponding err
or/
status bit
LED displays
Bus module
LINK 1 / LINK 2
ACT 1 / ACT 2
SF
BF
DIA
US1
MAINT
PS
0x10C
Parameter
setting error
The assembly
has detected a
parameter setting
error.
Parameter setting
errors can be:
- The assembly
cannot evaluate
any parameters
(examples of
possible causes:
unknown param-
eters, invalid
parameter combi-
nation).
- No parameters
have been as-
signed yet to the
assembly.
Applica-
tion fault
Latching
Check
parameters
and correct
these. Then
load the
parameters
into the
assembly
again.
2x