MAN20001572-01-07/22 (translation of the original operating instructions)
Operating Instructions Bus Module
MBM-PN-..-MLI-… (PROFINET)
EN
10.3.2. Remote mounting
Pay attention to the following points on remote mounting:
Ì
The maximum cable length for a line must not exceed 40 m.
Ì
Up to 3 base units can be operated per line. If you require a different configuration, contact our technical support team.
Ì
A maximum of 18 modules or submodules can be operated on one bus module MBM. Submodules count as one module
here. Attention is to be paid to the maximum permissible total current consumption (see
Ì
The number of safe devices in an overall system is limited to 12.
Ì
Always use the module plug connector ML1C, ML2C or both for remote mounting.
Ì
Lay the cable so that it is protected against damage as far as possible.
Ì
Make sure a sealing cap is fitted to unused connections.
Ì
Make sure the connecting cables are correctly screwed into place to achieve the stated degree of protection.
Before remote mounting, the sealing cap must be unscrewed from connection ML1C. The sealing cap for connection ML1D
is used as a tool for this purpose (see figure below). On the use of a second line, the sealing cap ML2C must also be un-
screwed. Then the sealing cap for connection ML1D must be re-fitted.
1
3
2