W
ATLOW
®
EZ-ZONE
®
RMZ4
-
51
-
E
THER
CAT
®
A
DAPTER
Alarm Group 8 Output
Zone
0x5F00
0x69
0x2F
Defines which zone on the bus hosts the alarm
group 8 output.
Alarm Group 8 Output
Instance
0x5F00
0x69
0x30
Defines which output in the zone implements
the digital alarm group 8 output.
Alarm Picking
Each sub index corresponds to a control loop module’s involvement. For each group
select with alarm actions of a loop get incorporated in that alarm group.
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Alarm Group 1 Pick
List
0x5F01
0x6A
0x01
Determines how alarms from loop 1 map
into the group.
0 = Not part of the group
1 = Process alarms activate the group
2 = Non occurring process alarms activate the group
3 = Deviation alarms activate the group
4 = Non occurring deviation alarms activate the group
5 = A process AND a deviation alarm with activate the
group
6 = A process OR a deviation alarm will activate the
group.
0x5F01
0x6A
0x02
Determines how alarms from loop 2 map
into group 1.
….
….
For each loop…
0x5F01
0x6A
0x30
Determines how alarms from loop 48 map
into group 1.
Alarm Group 2 Pick
List
0x5F02
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 2.
Alarm Group 3 Pick
List
0x5F03
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 3.
Alarm Group 4 Pick
List
0x5F04
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 4.
Alarm Group 5 Pick
List
0x5F05
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 5.
Alarm Group 6 Pick
List
0x5F06
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 6.
Alarm Group 7 Pick
List
0x5F07
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 7.
Alarm Group 8 Pick
List
0x5F08
0x6A
0x01 … 0x30 Determines how alarms from loop nn map
into group 8.
Using