heat and cooling actions will happen
simultaneously in the band. This allows heat to
modulate a less agile cooling system.
Ramp to Set Point Enable
0x4nn1
0x68
0x20
Enables set point ramping. If enabled, changes
in set point will cause the actual set point to
ramp from the current PV to the target SP at
the programmed rate.
0 = Off
1 = Start Up
2 = Set Point Change
3 = Both
Ramp to Set Point Rate
0x4nn1
0x68
0x21
Defines the rate of set point ramping in degrees
per minute.
Safe State Action
0x8nn0
0x6D
0x16
How the control operates in the Safe State.
Loop Off (default), Manual, Standby Auto, or
Nominally.
0 = Actual Control State (0x6nnn SI 0x01) = OFF
1 = Actual Control State (0x6nnn SI 0x01) =
ON, Actual Control Mode (0x6nnn SI 0x02) =
AUTO, Controlling Set Point (0x6nnn SI 0x16) =
Target Set Point (0x7nnn SI 0x11)
2 = Actual Control State (0x6nnn SI 0x01) = ON,
Actual Control Mode (0x6nnn SI 0x02) = AUTO,
Controlling Set Point (0x6nnn SI 0x16)= Standby
Set Point (0x8nnn SI 0x20)
3 = Actual Control State (0x6nnn SI 0x01) = ON,
Actual Control Mode (0x6nnn SI 0x02) =
MANUAL, Manipulated Value (0x6nnn 0x12) =
Forced MV (0x7nnn SI 0x12)
4 = Operate as configured
Standby Set Point
0x8nn0
0x6D
0x20
Sets an alternate Set Point which way be used
in the safe state to keep the system operational
at a nominal set point.
Set Point High Limit
0x8nn0
0x6D
0x21
Defines the upper settable Target Set Point
value. Use to ensure the set point is in an
acceptable range.
Set Point Low Limit
0x8nn0
0x6D
0x22
Defines the lowest settable Target Set Point
value. Use to ensure the set point is in an
acceptable range.
MV High Limit
0x8nn0
0x6D
0x24
Defines the upper settable Forced MV value.
Use to ensure the set manual power is in an
acceptable range.