W
ATLOW
®
EZ-ZONE
®
RMZ4
-
43
-
E
THER
CAT
®
A
DAPTER
Alarm 1 High Set Point
0x8nn0
0x6D
0x2C
The point where a high alarm 1 becomes
active. This is an absolute temperature.
Alarm 1 Low Set Point
0x8nn0
0x6D
0x2D
The point where a low alarm 1 becomes
active. This is an absolute temperature.
Alarm 1 Set Point Upper
Bound
0x8nn0
0x6D
0x2E
Alarm 1 High Set Point cannot be set above
this value. This is typically set as the
maximum allowable for the tool.
Alarm 1 Set Point Lower
Bound
0x8nn0
0x6D
0x2F
Alarm 1 Low Set Point cannot be set below
this value. This is typically set as the
minimum allowable for the tool.
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Alarm 2 Enable
0x8nn0
0x6D
0x15
0 = Disable the deviation alarm
1 = Enabled the deviation alarm
Alarm 2 High Set Point
0x8nn0
0x6D
0x30
The point where a high alarm 2 becomes
active. This is a temperature relative to this
loops set point, typically a positive number
like 20C.
Alarm 2 Low Set Point
0x8nn0
0x6D
0x31
The point where a low alarm 2 becomes
active. This is a temperature relative to this
loops set point, typically a negative number
like -20C.
Alarm 2 Set Point Upper
Bound
0x8nn0
0x6D
0x32
Alarm 2 High Set Point cannot be set above
this value. This is typically set as the
maximum allowable for the tool.
Alarm 2 Set Point Lower
Bound
0x8nn0
0x6D
0x33
Alarm 2 Low Set Point cannot be set below
this value. This is typically set as the
minimum allowable for the tool.
Using
Parameter
ECAT
Index
DNET
Class
Sub
/Attr
Description
Alarm Condition
0x6nn0
0x6B
0x17
For each loop with will indicate if either of
the 2 alarms is active.
0x0001 = Process alarm condition present
0x0002 = Deviation alarm condition present
0x0003 = Both alarm conditions present