Paradigm Architectural Control Processor Configuration Manual
Service and Maintenance
Replace a Paradigm ACP
Step 1:
Open enclosure door.
Step 2:
If possible, save all configuration files to removable media.
When the Paradigm ACP is hosted by a Unison DRd
action also saves the dimming rack
configuration with the architectural configuration.
Step 3:
Remove the existing Paradigm ACP from the rack.
a: Hold both sides of the Paradigm ACP and pull straight out.
Step 4:
Remove the CompactFlash card from the existing Paradigm ACP and insert it
into the new Paradigm ACP.
Step 5:
Insert the new Paradigm ACP into the enclosure.
a: Rest the Paradigm ACP on the bottom lip of the enclosure.
b: Slide the ACP into the rack.
c: Press on each corner of the ACP to ensure proper connection with the card
edge connector’s on the left and right I/O boards. If power is applied, the
status LEDs will illuminate when proper connection is made.
Step 6:
If the Paradigm ACP is installed within a Unison DRd rack and a configuration
mismatch error occurs, select “Yes” to load the dimming configuration from the
DRd rack dimming engine. Alternatively you could select “NO”, then proceed to
load the rack configuration from the removable media.
Step 7:
Load the Paradigm ACP configuration from the removable media.
Architectural Configuration” on page 61.
N o t e :
Both the architectural and dimming configurations are stored to the removable
CompactFlash.
N o t e :
If you don’t get a configuration mismatch error, the Paradigm ACP already has the
matching dimming rack configuration or it doesn’t have any dimming rack
configuration file and therefore automatically loaded the dimming configuration
from the DRd rack dimming engine.