Electrical connections
Circuit board HA-C5
63
These terminals have already been pre-wired at the factory:
Terminal
Function
Default assignment
CAN Node
CAN-Bus node switch
F10
Fuse 230 V, T 5 A (electronics)
F11
Fuse 230 V, T 8 A (Motor: [L1])
F12
Fuse 230 V, T 5 A (ignition)
F13
Fuse 230 V, T 8 A (Motor: [L2])
F14
Fuse 230 V, T 5 A ([S46]: [L3], [S48]: [L3])
F15
Fuse 230 V, T 8 A (Motor: [L3])
S40
230 V output
Pellet discharge conveyor and stoker screw
S41
230 V output
Dosing screw
S42
Locked supply extension 400 V
Cannot be used
S43
Locked supply extension 230 V
Cannot be used
S44
400 V supply
Mains power input (via contactor)
S45
230 V output
Ignition
S46
230 V output
Supply for draught fan
S47
230 V input
Mains switch
S48
230 V output
Boiler pump
S50
Supply extension 230 V
to mains adapter
S51
Supply extension 230 V
to circuit board [GM-C]: terminal [S1]
S53 STB
230 V input
Safety temperature limiter (Safety temperature lim-
iter (STB))
S53 ASCHENKÜBEL 230 V input
Ash box switch
S53 ROST
230 V input
Grate switch
S53 GLUTBETT
230 V input
Firebed switch
S54
230 V input
Cannot be used
S55
230 V input
Cannot be used
S56
230 V input
Cannot be used
S57
230 V output
Pellet vacuum turbine (via contactor)
S58
230 V output
Drive for heat exchanger cleaner
S59
230 V output
Tilting grate
S60
230 V output
Ash screw
S61
230 V output
Return riser mixing valve
S63
230 V input
Boiler maintenance switch
S64
230 V input
Only for precipitator: supply for the high voltage
units
S537
24 V AC/DC output /
Analogue input
Actuator air valve: primary air
S538
24 V AC/DC output /
Analogue input
Actuator for air valve: secondary air
S539
24 V AC/DC output /
Analogue input
Supply and actual position of the flue gas recircula-
tion
S540A
RS-485 bus (for frequency converter) Cannot be used
S540B
RS-485 bus (for frequency converter) Cannot be used
Summary of Contents for 13180 LP-D
Page 1: ...2020 04 21 EN 0000000475 V 006 5402 00 939091 002 Pellet boiler ePE K 180 240 kW Installation ...
Page 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33 ...
Page 55: ...Installation Network connection 55 ...
Page 61: ...Electrical connections Overview of circuit boards 61 ...
Page 65: ...Electrical connections Circuit board HA C5 65 ...
Page 85: ......
Page 86: ...www eta co at ...
Page 87: ......
Page 88: ...www eta co at www eta co at downloads DOWNLOAD ...