36
www.eta.co.at
External Tichelmann
Buffer storage tank
8.5
External Tichelmann
Parallel buffer connection with external Tichelmann
The basic principle of the external Tichelmann is parallel flow through several buffer storage tanks, which is achieved
with diagonally opposed connection of the collectors. The last buffer on the flow collector is the first on the return
collector. To achieve uniform charging and discharging, the connection pipes should be at least one or two sizes
smaller than the collector. There is no output limit for this circuit. To minimize pipe circulation losses, it is helpful to
make the connections with downward siphon loops.
For a small solar heating system, the total volume can be reduced in the summer by locking individual buffers.
With hot water tank or internal water heat exchanger
1
Boiler, heating circuits, oil/gas boiler flow
2
Temperature sensor [Sensor 1 (upper)]
3
Temperature sensor [Sensor 2]
4
Oil/gas boiler return
5
Temperature sensor [Sensor 3]
6
Solar flow
7
Temperature sensor [Sensor 4]
8
Boiler, high-temperature circuit return
9
Solar return
10 Low-temperature circuits return
11 Hot water
12 Cold water
maximum total output
Connecting ball valves on buf-
fer
Collector line at least
30 kW
DN 20
DN 25
R 1"
28 x 1.5
60 kW
DN 25
DN32
R 1¼"
35 x 1.5
Summary of Contents for 13180 LP-D
Page 1: ...2020 04 21 EN 0000000475 V 006 5402 00 939091 002 Pellet boiler ePE K 180 240 kW Installation ...
Page 33: ...Buffer storage tank Connection between multiple buffer storage tanks 33 ...
Page 55: ...Installation Network connection 55 ...
Page 61: ...Electrical connections Overview of circuit boards 61 ...
Page 65: ...Electrical connections Circuit board HA C5 65 ...
Page 85: ......
Page 86: ...www eta co at ...
Page 87: ......
Page 88: ...www eta co at www eta co at downloads DOWNLOAD ...