Manual control via push button
password is set, the motion detector locks automatically. You can unlock
the motion detector again by entering the selected password.
To remove
< password protection >
again, enter the current password and
then set 0000 as the new password. Alternatively, you can completely
disconnect the device from the mains voltage for one minute.
Acknowledgement:
The lighting switches on. After the change has been
completed, the violet detector LED flashes four times to indicate that the
infrared signal has been successfully received. The lighting then switches
off. If the password is entered incorrectly or there is a transmission fault,
the detector LED flashes violet – red – violet – violet.
8.
Manual control via push button
The motion detector is equipped with a connection for an external push
button (S terminal, for information on connection see chapter
Standard operation with additional control using a push button" on page
21
). This means that the motion detector can be manually overridden at
any time so that the lighting can be switched on or off individually.
The motion detector switches the lighting
on or off
until …
•
it detects a movement
or
•
until an external push button is pressed again
and
•
until the configured switch-off delay time has elapsed
Once this time has elapsed, the motion detector switches back to the
configured operating mode.