Programming
WED FEB 6, 1994 11:16:35 Remote Alpha-Numeric Display Network
MESSAGE ENTRY/EDITING for SELECTED DISPLAY
Current Project File: Selected Display: FCC
Project Name: Printer:
Location: Baud Rate:
Annunciation Type(s): Routing:
Active When Enabled: Current Msg:
Active When Disabled: Total Msgs:
_____________ _____________
Line: Panel: Zone: [_____________] [_____________]
INSTRUCTIONS
Press UP or DN ARROW Keys until the desired line value appears above.
Choices 0, 2, 4, or 6
Press RT ARROW to enter panel
Press ENTER key to accept value shown, then do panel.
Press ESC to exit from message entry.
FCC Message Entry/Edit Screen
Configuring the Balance of Annunciators on an FCC Network
When the first annunciator (address 01) has been completely
configured, return to the opening screen and increment the Selected
Display parameter to the next annunciator address and
repeat
programming
Phase 2
for the next annunciator. When all annunciators
have been configured, proceed to the Downloading to the LSRA
section of this chapter for instructions on downloading.
Note:
The DCPU port should be configured in the DCPU database as a
“Display” port using the FCC Compiler Program.
LSS4 Configuration
LSS4 Programming Notes
When connected to an LSS4 panel (Figure Chapter 3-7), the LSRA
annunciator is defined as device address #15. RSA4-CPUs used with
point annunciators may be used with the LSRA on the LSS4 RS-485
circuit as long as there are no more than four life safety remote
annunciators total on the circuit. The remote annunciator’s sub-
addresses must not conflict. Refer to the LSS4 section of the
Configuration Program section for additional details. Each LSRA is
optically isolated from the panel. A remote RS-485 Interface Card (P/N
130285) is required to connect the remote annunciator circuit to older
LSS4 panels without the RS-485E terminals on TB4.
Phase 1 - Parameter Entry for Entire Project
The “Parameter Entry for Entire Project” screen is divided into three
sections: the Status Window (top), the Menu Window (middle), and the
Instructions Window (bottom), as shown in the LSS4 menu below.
Current time and date information is displayed above the status
window. The Status Window shows the current settings of the
annunciator parameters.
LSRA
Installation, Operation, Maintenance, and Configuration Manual
4.15
firealarmresources.com