ESP Safety UPES-50D Operating Manual Download Page 37

37 

 

Parameter 

Word 
address, 
hex 

Data 
type 

Details 

Setting 2 cards 
(R/W) 

0x0005  BYTE 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Setting 3 cards 
(R/W) 

0x0006  BYTE 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Setting 4 cards 
(R/W) 

0x0007  BYTE 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Setting 5 cards 
(R/W) 

0x0008  BYTE 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Setting 6 cards 
(R/W) 

0x0009  BYTE 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Setting 7 cards 
(R/W) 

0x000A  BYTE 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Setting 8 cards 
(R/W) 

0x000B  BYTE

 

High byte – communication mode. 
Lower byte – exchange rate of two ports with 
sensors. 

Device identification 
(R) 

0x000C  BYTE

 

Lower byte – device model = 0х08; 
High byte – device type = 0х03 (gas 
analytical system). 

Card availability bit field 
(R) 

0х000D  BYTE 

Lower byte. 
0 bit (lower): 1 – 1 card set 
                               0 – no 1 card; 
1 bit: 1 – 2 cards set 
           0 – no 2 card; 
… 
7 bit: 1 – 8 cards set 
           0 – no 8 card. 

Alarm reset 
by cards 
(W) 

0x000E  BYTE 

Lower byte. 
0 bit– 1 card: 1 – alarm reset; 
1 bit - 2 card: 1 – alarm reset; 
…. 
7 bit – 8 card: 1 – alarm reset. 

Information on the state of the sensors connected to the channel boards 

Concentration of 1 sensor of 
1 channel card 
(R) 

0x0100  WORD 

Concentration, measured by the sensor 
(see note 2) 

Measurement accuracy of 1 
sensor of 1 channel card 
(R) 

0х0101  BYTE 

Measurement accuracy (see note 2) 

Concentration of 2 sensor of 
1 channel card 
(R) 

0x0102  WORD  Concentration measured by the sensor.  

Summary of Contents for UPES-50D

Page 1: ...UPES 50D Digital RS485 Multi Channel Controller Operating Manual...

Page 2: ...gramming Tree Diagrams 18 UPES Menu in the Absence of the channel boards 18 UPES Menu with the Channel Boards Installed 21 UPES Channel Programming 22 UPES Channel Board Com Ports Operation Mode Setti...

Page 3: ...ctors SGOES TGAES Rx TGAES Tx SSS 903 IPES IR UV IPES IR3 The UPES multi channel controller consists of a control panel capable of connecting up to 16X8 devices via RS485 From 1 to 128 devices can be...

Page 4: ...unit of BP 10 design 130 242 V 50 Hz main power or direct current with voltage 180 340 V backup power UPES power from DC power supply with voltage not more than V 24 UPES commutated current at AC vol...

Page 5: ...5 UPES Device Fig 2 UPES Device 1 CPU board 2 8 channel boards with 2 communications lines RS485 3 Power supply unit Fig 2 1 Front View 1 Interconnection board 2 Blind panel 2 3 1 2 1...

Page 6: ...S ON OFF button 2 LED display 3 Buzzer 4 Keyboard Each channel of the threshold device has a corresponding LED group 2 green Activating 24V at the output of the module 4 red exceeding specified thresh...

Page 7: ...communication channel it is possible to use any shielded twisted pair cables In this case signal wires are connected to contacts 485 and 485 and the shield is connected to contact GND located at the...

Page 8: ...connected to each port The state of the sensors connected to the first port is displayed on the first relay set and the state of the sensors connected to the second port on the second relay set The f...

Page 9: ...displayed on it it immediately turns on threshold LEDs and the threshold relay with the set delay NOTE It is NOT possible to connect on single sensor board gas detectors and flame detectors including...

Page 10: ...ter ____________________________________________________________________________ 1 channel 2 serial number of the channel board 3 serial number of the sensor connected to the channel board 4 operating...

Page 11: ...r m a F R E 6 7 C h a n 1 7 7 F i r e F R E C h a n 1 7 7 F a u l t F R E 1 channel 2 serial number of the channel board 3 serial number of the sensor connected to the channel board 4 operating mode o...

Page 12: ...size of 3U 19 482 266 132 mm built in accordance with the bus structured and modular approach In the frame there is a power supply module CPU module and up to eight two channel modules The power suppl...

Page 13: ...is indicated by the single sound signal for 1 second Operating Mode Alarms of the Power Supply Indication Mode UPES Power Supply Intermittent green illumination of the UPES power button UPES is not tu...

Page 14: ...nce of the earthing device that shall not be more than 4 Ohm UPES Installation Clearance Consideration When installing the control panel in a rack there shall be empty space above it and below it that...

Page 15: ...play The top line displays the channel number and the search percentage completion and in the bottom line displays the search mode Search search all types of sensors in all the MODBUS addresses from 1...

Page 16: ...arm and relay trigger The LED is faulty Replace the LED The authorized specialist shall perform this operation The threshold is exceeded but external devices are not switched on The relay is faulty Da...

Page 17: ...oes not switch on All input voltage 220V is lost when the UPES has already been on Connect the power supply to UPES Short term red flashes of the UPES power button no sound signals UPES does not switc...

Page 18: ...om any menu item without setting the selected value by press the Control Exit button To set the UPES exchange speed with the top level system select the button Prog button of the Exchange rate menu an...

Page 19: ...19 Figure T1...

Page 20: ...tors 9600 baud The UPES setup menu is similar to the menu when there are no channel boards fig Error Reference source not found except that if there are channel cards the menu items related to exchang...

Page 21: ...d whose number is displayed in the top line of the display during the normal operation mode If you want to select the setup menu for the channel board with a different number from the one that appears...

Page 22: ...press again the Prog button then you get into the channel board setup menu fig T3 Figure T3 In the channel board there are two sets of relays 1 and 2 of the threshold When connecting the channel boar...

Page 23: ...e second port To select the edited relay kit select Programming Channel x Comp 1 where is the number of the channel being edited To select the second relay set press the or button and the menu Program...

Page 24: ...and buttons and press the Test Enter button When the sensor threshold is achieved the relay delay triggering can be set by the appropriate threshold to do so it is required to select Relay 1 delay or...

Page 25: ...t the communication is restored in the initial mode Ring communication with sensors via the first port where the ring integrity is controlled When the ring is open communication between the primary tr...

Page 26: ...o copy and press the Test Enter button Then press the Prog button and you will enter the set selection menu where to copy the settings Use the or buttons to select the desired channel and the desired...

Page 27: ...In this menu you can set the sensor search by the known address address search type search by type address and type search by the list or simply search Auto search as well as erase the list of sensor...

Page 28: ...g button The data about the sensors will be deleted from the channel board memory and the central boards controller will return to the menu title All the thresholds communication failure flags are res...

Page 29: ...top line contains the number of the channel board in which the search for the sensor will be performed and the ordinal number of the sensor If the channel board is set to the operation mode with two...

Page 30: ...ensors When you have entered the desired address press the Test Enter button to record the address in memory this address will be in the square brackets To edit the MODBUS address of the next sensor i...

Page 31: ...e address will be detected automatically The sensors with the None type will not participate in the search The sensor types shall be to filled in starting with the first sensor With the and buttons se...

Page 32: ...32 Figure T11...

Page 33: ...g T8 Before you start the search by the list you need to set the list of sensor types and addresses Pressing the Prog button enter the sensor list setup menu The list of sensors is filled in in a mann...

Page 34: ...modes Setting the necessary number of sensors press the Prog button until the menu appears The search program is started in the same way When the search is complete the display will display the number...

Page 35: ...T8 and press the Prog button and go to the Search program start menu fig T13 Figure T13 The search program is started in the same way When the search is complete the display will display the number of...

Page 36: ...bus address 1 247 Device exchange rate R W 0x0001 BYTE Lower byte exchange rate with the top level For the two ports the same rate is set 2 4800 baud 3 9600 baud 4 19200 baud 5 57600 baud 6 115200 bau...

Page 37: ...wo ports with sensors Setting 8 cards R W 0x000B BYTE High byte communication mode Lower byte exchange rate of two ports with sensors Device identification R 0x000C BYTE Lower byte device model 0 08 H...

Page 38: ...09 BYTE Measurement accuracy Concentration of 6 sensor of 1 channel card R 0x010A WORD Concentration measured by the sensor Measurement accuracy of 6 sensor of 1 channel card R 0 010B BYTE Measurement...

Page 39: ...entration measured by the sensor Measurement accuracy of 13 sensor of 1 channel card R 0 0119 BYTE Measurement accuracy Concentration of 14 sensor of 1 channel card R 0x011A WORD Concentration measure...

Page 40: ...gering of 1 16 sensor of 1 channel card R 0x0201 WORD Triggering flags bit field 0 bit lower 1 sensor 15 bit 16 sensor Defect relay triggering flag of 1 16 sensor of 1 channel card R 0x0202 WORD Trigg...

Page 41: ...te of the even sensor Units of measurement of 7 and 8 sensor of 1 channel card R 0 0233 BYTE High byte odd sensor units of measurement code lower byte of the even sensor Units of measurement of 9 and...

Page 42: ...e lower byte even sensor type code Type of 9 10 sensor of 1 channel card R 0x0274 BYTE High byte odd sensor type code lower byte even sensor type code Type of 11 12 sensor of 1 channel card R 0x0275 B...

Page 43: ...nits of the parameter by the sensor 1 threshold of 2 sensor of 1 channel card R 0 02F1 WORD 1 threshold value of this register 10 measurement accuracy in the measurement units of the parameter by the...

Page 44: ...166 167 186 187 1A6 1A7 1C6 1C7 1E6 1E7 5 108 109 128 129 148 149 168 169 188 189 1A8 1A9 1C8 1C9 1E8 1E9 6 10A 10B 12A 12B 14A 14B 16A 16B 18A 18B 1AA 1AB 1CA 1CB 1EA 1EB 7 10C 10D 12C 12D 14C 14D 16...

Page 45: ...ensor Channel Card No 1 2 3 4 5 6 7 8 1 2 2B0 2B8 2C0 2C8 2D0 2D8 2E0 2E8 3 4 2B1 2B9 2C1 2C9 2D1 2D9 2E1 2E9 5 6 2B2 2BA 2C2 2CA 2D2 2DA 2E2 2EA 7 8 2B3 2BB 2C3 2CB 2D3 2DB 2E3 2EB 9 10 2B4 2BC 2C4 2...

Page 46: ...y Sensors Sensor Channel Card No 1 2 3 4 5 6 7 8 1 2 400 408 410 418 420 428 430 438 3 4 401 409 411 419 421 429 431 439 5 6 402 40A 412 41A 422 42A 432 43A 7 8 403 40B 413 41B 423 42B 433 43B 9 10 40...

Page 47: ...TO Ethylene oxide 55 DTM Diethylamine 56 IBN Isobutylene 57 HCL hydrogen chloride 58 HF hydrogen fluoride 59 not used Not used 60 MMP methyl mercaptan 61 EMP ethyl mercaptan 62 NAC nitric acid 63 NO n...

Page 48: ...wer Cable Connection Diagram Wiring Diagrams for Flame Detectors Alterating current from mains 220V 50Hz Contact Mains 1 220V 2 Grounding 3 220V UPES Connector P587 Mains Contact 220V 1 Grounding 2 22...

Page 49: ...49 Wiring Diagrams for Gas Detectors UPES Markings The UPES device has the following marking manufacturing plant trademark b UPES conventional designation c serial number d year of manufacture...

Page 50: ...ing shall be performed in accordance with the cyclogram specified in this manual Programming of other UPES parameters shall be also performed in accordance with the cyclogram specified in this OM Prev...

Page 51: ...uency maintenance check every day maintenance once per quarter technical repair once pert year major overhaul once per 5 years Warranties ESP Safety Inc 555 N First Street San Jose CA 95112 USA guaran...

Reviews: