37
Parameter
Word
address,
hex
Data
type
Details
Setting 2 cards
(R/W)
0x0005 BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Setting 3 cards
(R/W)
0x0006 BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Setting 4 cards
(R/W)
0x0007 BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Setting 5 cards
(R/W)
0x0008 BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Setting 6 cards
(R/W)
0x0009 BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Setting 7 cards
(R/W)
0x000A BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Setting 8 cards
(R/W)
0x000B BYTE
High byte – communication mode.
Lower byte – exchange rate of two ports with
sensors.
Device identification
(R)
0x000C BYTE
Lower byte – device model = 0х08;
High byte – device type = 0х03 (gas
analytical system).
Card availability bit field
(R)
0х000D BYTE
Lower byte.
0 bit (lower): 1 – 1 card set
0 – no 1 card;
1 bit: 1 – 2 cards set
0 – no 2 card;
…
7 bit: 1 – 8 cards set
0 – no 8 card.
Alarm reset
by cards
(W)
0x000E BYTE
Lower byte.
0 bit– 1 card: 1 – alarm reset;
1 bit - 2 card: 1 – alarm reset;
….
7 bit – 8 card: 1 – alarm reset.
Information on the state of the sensors connected to the channel boards
Concentration of 1 sensor of
1 channel card
(R)
0x0100 WORD
Concentration, measured by the sensor
(see note 2)
Measurement accuracy of 1
sensor of 1 channel card
(R)
0х0101 BYTE
Measurement accuracy (see note 2)
Concentration of 2 sensor of
1 channel card
(R)
0x0102 WORD Concentration measured by the sensor.