18
Description of the UPES
Menu with Tree Diagrams
The
UPES
menu in the absence of channel boards
Depending on the UPES state, availability of channel boards, availability and condition of
sensors there may be various menu items. In order to enter the menu, press the(“Prog”) button.
If there are no channel boards in UPES, there is only one menu for setting —("UPES
Programming") (Fig.T1).
In this mode, the UPES only the interface language, the exchange rate with the top-level system,
and UPES MODBUS address can be set.
To configure the interface language use the (“Prog”) button to select "Language" and the "+" and
"−" buttons to select the desired language and press the (“Test/Enter”) button. To exit from any
menu item without setting the selected value by press the (“Control/Exit”) button.
To set the UPES exchange speed with the top-level system, select the button ("Prog") button of
the (“Exchange rate”) menu and use the "+" and "−" buttons to select the desired exchange rate.
The following exchange rates are possible with the top-level system: 4800, 9600, 19200, 57600
baud. To save the set exchange rate, press the (“Test/Enter”), and the selected value will be in
the square brackets.
To set the UPES MODBUS address in the top-level system select the (Modbus address) menu.
The available range of addresses to set is from 1 to 247. Select the address required with the «+»
and «−» buttons. Select and press the «+» or «−», to move the Modbus addresses faster. For the
selected address to be set and recorded in the controller memory, press the (“Test/Enter”) button,
the selected Modbus address value will be in square brackets.