6.1.2.4 Test Data Transfer
In the online mode the data transfer can be tested.
If you are not already in this mode, change into the online mode by clicking the
Online
button.
Then click the
Free run
button to switch into
Free run
mode.
The states of the slaves and of the master should be
Operational
after a short time, as indicated by
the -symbols in Fig. 10.
Fig. 10:
EtherCAT Workbench with ECX-EC in
Operational
state
If the states are
Operational
In case of problems please check the outputs in the EtherCAT Workbench and read the following
note.
INFORMATION
The most probable reason of the problem that might occur here is that different
configurations for primary and secondary side have been created at the configuration of
the variables. In this case the ECX-EC does not switch into
Operational
or
Safe-
Operational
(with error
Inconsistent Settings
–
Al Statuscode
0x0026).
Make sure that the input variables of the primary side comply with the output variables
of the secondary side and vice versa (the name of the variables can be disregarded).