Device Profile Area
Manual • Doc.-No.: C.3012.21 / Rev. 1.1 CAN-CBX-REL4
Page 86 of 99
7.10.5 Error Value Output 8-bit (6207
h
)
On condition that the corresponding error mode (object 6206
h
) is enabled, device errors shall switch the
relays to the error value defined in this object.
Index
Sub-
index
Description
Value
range
Default
Data type
Access
6207
h
0
number_of_output 8 bit
1
1
unsigned 8
const
1
error_value_output_8-bit
00...0F
h
0
unsigned 8
rw
Assignment of the variable error_value_output_8-bit:
Bit:
7
6
5
4
3
2
1
0
Relay:
-
-
-
-
Rel_4
Rel_3
Rel_2
Rel_1
This variable contains the value, a relay is set to if an error occurs.
Bit value Rel_x
Meaning
0
If object 6206
h
is enabled, relay x will be de-energized in case of fault.
1
If object 6206
h
is enabled, relay x will be energized in case of fault.