Hardware-Installation
Manual • Doc.-No.: C.3012.21 / Rev. 1.1 CAN-CBX-REL4
Page 16 of 99
3.2.4 Operation of the CANopen-Status LED
LED indication
Display function
Label
Name
Colour
Indicator
state
Description
S
CANopen
Status
green
blinking
Pre-operational
on
Operational
1 flash
Stopped
3 flashes
Module is in bootloader mode, the power LED is off,
(or coding switch position ID-node > 7F
h
when
switching on; see page 17)
Table 8: Indicator states of the CANopen Status-LED
3.2.5 Operation of the Error-LED
LED indication
Display function
Label
Name
Colour
Indicator state
Description
M
Error
red
off
no error
on
error on an error-controlled output
- if the module has switched to the state stopped due to an
error, the LED remains on, even if the error is no longer
existing
- errors that occur after changing to stopped state are not
indicated
2 flashes
Internal software error
e.g.:
- stored data have an invalid checksum therefore default
values are loaded
- internal watchdog has triggered
- indicator state is continued until the module resets or an
error occurs at the outputs.
Table 9: Indicator state of the Error-LED