34
•
Press
DOWN
button
until
you
find
below
message:
‐
ADC
A/F
:
Show
actual
ADC
value
from
airflow
velocity
sensor.
‐
ADC
ZERO
:
ADC
value
from
airflow
velocity
sensor
when
air
velocity
is
zero
(set
during
zero
calibration)
‐
ADC
MIN
:ADC
value
from
airflow
velocity
sensor
at
airflow
failure
point
(set
during
sensor
calibration).
‐
ADC
MAX
:
ADC
value
from
airflow
velocity
sensor
at
airflow
maximum
point
(set
during
sensor
calibration).
‐
ADCTEMP
:
ADC
value
from
temperature
sensor.
‐
TEMP
:
this
is
the
current
ambient
temperature
read
by
temperature
sensor
(in
ºC)
‐
CONSTANT
:
this
is
the
airflow
sensor
constant
‐
CHM
SNSR
:
ADC
value
from
chemical
sensor.
•
In
order
to
prevent
any
AIRFAIL
or
unstable
velocity
displayed
on
LCD
problem,
please
ensure
the
followings
after
the
calibration
done:
1.
CONSTANT
value
is
correct.
Check
it
with
constant
written
on
sensor
body
or
inside
Replaceable
Component
Record
List
which
come
with
test
report.
2.
TEMP
shows
room
temperature.
If
not,
refer
to
nextpossible
cause,part
B.
3.
ADC
ZERO
<
ADC
MIN
<
ADC
MAX.
If
not
please
re
‐
do
calibration
in
correct
sequence:
SET
CONSTANT
→
SET
ZERO
→
CALIB.
If
CALIBRATION
ERROR
is
encountered,
please
refer
to
next
possible
cause,
part
A.
4.
Just
after
calibration,
ADC
A/F
value
should
be
somewhere
between
ADC
MIN
and
ADC
MAX.
If
not,
please
adjust
the
speed
controller
or
redo
calibration
as
necessary.
Sensor
Failure
/
Sensor
Misalignment
A.
Air
Flow
Sensor
failure
/
misalignment
•
Airflow
sensor
is
located
inside
the
unit
and
can
be
accessed
from
the
back.
See
figure
3
‐
2
below.
It
is
a
stainless
steel
tube
with
2
round
holes
facing
up.
Important
to
check:
1.
Ensure
that
the
sensor
area
is
not
blocked
at
all
and
that
its
through
‐
holes
are
perpendicular
to
the
filter’s
surface.
2.
Exhaust
sensor
is
attached
tightly
to
the
mounting
plate.
3.
There
is
no
gap
between
sensor
box
and
filter
surface.
4.
Sensor
box
is
installed
tightly
to
the
cabinet.
•
Turn
off
the
cabinet.
•
See
Component
Layout
to
locate
the
main
board.
•
Using
DVM,
check
the
sensor’s
output
voltage
(DC)
at
channel
AIN1(+)
and
J1(
‐
)
on
main
board
(See
drawing
3
‐
3
below).
•
The
voltage
should
increase
if
motor
voltage
is
increased
and
decrease
if
motor
voltage
is
decreased.
•
If
your
observation
is
different,
check
sensor
connection
on
the
unit
(see
figure
3
‐
6
below)
and
at
connector
D
pin
9,10,11,12
on
electrical
box
(see
Layout
at
the
end
of
this
section)
for
any
bad/loose
connection.
•
If
connection
is
okay
but
sensor
is
still
not
working
properly,
replace
it.
•
If
airflow
sensor
is
working
properly,
proceed
to
next
step.
B.
Temperature
Sensor
Failure
•
Temperature
sensor
is
located
close
to
airflow
sensor
inside
the
unit.
See
figure
3
‐
2.
•
Using
DVM,
check
the
temperature
sensor’s
output
voltage
(DC)
at
channel
AIN4(
‐
)
and
J4(+)
on
main
board
(See
figure
3
‐
3
below).
•
0.01VDC
should
represent
one
degree
Celsius.
For
example,
if
output
is
0.25VDC,
it
indicates
temperature
of
25
o
C.
Tolerance
of
±1
o
C
is
acceptable.
•
Replace
temperature
sensor
if
the
reading
is
wrong.
•
If
temperature
sensor
is
working
properly,
proceed
to
next
step.
Summary of Contents for Ascent max
Page 6: ...iv...
Page 10: ...viii...
Page 22: ...12...
Page 26: ...16...
Page 60: ...50...
Page 61: ...51 Ductless Fume Hoods APPENDIX...
Page 70: ......