GB-3
D
GB
NL
RUS
PL
F
E
UA
CN
Chimney
CAUTION
The RGA 100 is only deemed CE tested and ap-
proved when used with the coaxial chimney de-
scribed in “Accessories”.
▷
Do not exceed the maximum length (5 m) of
the chimney.
▷
The design of the chimney depends on the prem-
ises and the roof construction.
▷
Various chimney elements for individual appli-
cations can be supplied, see page 21 (Ac-
cessories).
▷
The wall mounting bracket cannot be installed in
the correct position until the chimney has been
selected.
Siphon connection
DANGER
Risk of poisoning!
– If the RGA 100 is operated without a siphon
or with an empty siphon, toxic flue gases may
escape. If the RGA 100 is operated without a
siphon, the opening must remain unobstructed.
▷
A siphon must be connected before initial com-
missioning. This prevents the escape of toxic
flue gases and will also collect any condensate
contained in the flue gas.
▷
The siphon is not included in the delivery and
must be ordered separately for the nominal
diameter of 17.5 mm.
▷
Fill the siphon with water before initial commis-
sioning.
▷
If large volumes of condensate are discharged,
we recommend that an additional drain pipe is
connected to the siphon.
▷
If the heater has not been used for a lengthy
period, the siphon must be checked, cleaned
and filled with water before commissioning.
•
Unscrew the siphon, remove it and fill it until
water flows out of the side drain.
•
Secure the siphon again and ensure that the seal
is correctly positioned.
Connecting the gas supply
▷
The RGA 100 is set to the correct gas type as
specified in the purchase order.
▷
If you wish to use a different gas type, see
page 3 (Changing the gas type).
1
Disconnect the system from the electrical power
supply.
2
Shut off the gas supply.
3
Remove the sealing plug from the gas inlet on
the combination control on the underside of the
RGA 100.
4
Connect the gas pipe with an Rp ¾" threaded
connection or gas hose with an Rp ¾" connector,
see page 21 (Accessories).
▷
Use approved sealing material only.
5
MODE
RESET
ON/OFF
6
Changing the gas type
▷
If you wish to use a gas type other than the one
specified in the purchase order, the RGA 100
must be adjusted to the new gas type, see
page 10 (Adjusting the heater).
▷
Then seal the gas pressure setting.
▷
Note the new gas type on the type label with a
waterproof pen.