TROUBLESHOOTING
Page 15
PROBLEM
CAUSE
SOLUTION
Untreated water to
service
Open or defective bypass
Close or replace bypass
Water filter in regeneration
Wait until regeneration finishes or manually
advance regeneration to end
Valve body and timer out of synchronisation
Synchronise valve body and timer
Low level of filter media
Replenish filter media
Excessive service flow rate
Lower service flow rate
Increase filter capacity by increasing volume of filter
media
Leak at riser tube
Verify that riser tube is seated correctly and is not
cracked
Water filter fails to
start a regeneration
Faulty electrical supply
Verify electrical service (fuse, transformer,...)
Defective PCB
Replace PCB
Defective drive motor
Replace drive motor
Regeneration frequency not programmed
Program regeneration frequency
Loss of water pressure
Build-up of impurities in pressure tank
Clean filter media and control valve; increase
regeneration frequency
Plugged lower and/or upper distributor
Verify that distributors are free of debris
Crushed lower and/or upper distributor
Replace distributor(s)
Control valve cycles
continuously
Defective drive motor micro switch
Replace drive motor micro switches
Defective PCB
Replace PCB
Drain line from control
valve flows
continuously
Water filter in regeneration
Wait until regeneration finishes or manually
advance regeneration to end
Faulty electrical supply
Verify electrical service (fuse, transformer,...)
Defective drive motor
Replace drive motor
Defective micro switch
Replace micro switches
Defective PCB
Replace PCB
Valve body and timer out of synchronisation
Synchronise valve body and timer
Loss of filter media
Lower and/or upper distributor damaged
Replace distributor(s)
Leak between riser tube and upper distributor
Verify that riser tube is seated correctly and is not
cracked
Water filter fails to
backwash properly
Low operating pressure
Check operating pressure; must be higher than 2,0
bar
Insufficient water supply
Check water supply (flow rate/dynamic pressure)
Restricted drain line
Verify drain line for kinks or restrictions
Excessive build-up of impurities in pressure tank Clean or replace filter media and control valve;
increase regeneration frequency
Plugged backwash flow control
Clean or replace backwash flow control
Plugged top or bottom distributor
Verify that top and bottom distributor are clean and
slots are not clogged by iron or other impurities
Filter media is completely ‘caked’ (solid block)
Replace filter media and reduce regeneration
interval
Summary of Contents for pHneutralizer Series
Page 11: ...Page 11 ...
Page 14: ...HYDRAULIC FLOW DIAGRAMS Page 14 SERVICE BACKWASH PURGE ...
Page 18: ...EXPLODED VIEW SYSTEM Page 18 ...
Page 20: ...EXPLODED VIEW TIMER HEAD Page 20 ...
Page 22: ...EXPLODED VIEW VALVE BODY Page 22 ...
Page 25: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 1 a r 1 b 2 a 2 b 3 a 3 b ...
Page 26: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 4 a r 4 b 5 r 6 a r 6 b ...
Page 27: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 6 c 7 a 7 b r 7 c ...
Page 28: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 8 ...