ELECTRONIC CONTROL PANEL 

 

Page 8 

  

Picture 5

 

 

symbol 

button 

function 

 

SCROLL 

to advance to the next 

parameter 

 

UP 

to increase the value of the 

parameter 

 

DOWN 

to decrease the value of the 

parameter 

 

POWER-UP 

 
After power-up, the power LED will light up and the display 
will show the installed software version, f.e.: 
 
 
 
After 5 seconds, it will automatically revert back to the service 
mode. 
 

POWER FAILURE 

 
In  the  event  of  a  power  failure,  the  program  will  remain 
stored in the NOVRAM® during an undefined period, while an 
incorporated  SuperCap  (capacitor) will  maintain  the  correct 
time of day during a period of several hours; consequently, in 
case of prolonged power failure, the time of day might not be 
maintained; if this happens, the time of day will be reset to 
8:00  when  the  power  supply  is  re-established,  while  the 
indication will flash, indicating that the time of day needs to 
be set. 

 
 

 
When  the  power  failure  occurs  during  the  execution  of  an 
automatic  regeneration,  the  control  valve  will  remain  in  its 
last  position;  when  the  power  supply  is  re-established,  the 
control valve will return to the service position, stay there for 
60  sec.  and  restart  a  complete  regeneration  from  the 
beginning. 
 

TIMER FAILURE 

 
In  the  event  of  a  timer  failure,  the  display  will  show  the 
message: 
 
 
 
If powering off/on the water filter doesn’t solve this problem, 
professional service is required. 
 

SERVICE MODE 

 
In  service  mode  the display  shows the  time  of day and  the 
number of days remaining until the next regeneration: 
 
 

 

 
 
 
 

REGENERATION MODE 

 
In  regeneration  mode  the  display  shows  the  remaining 
regeneration time and the remaining cycle time: 
 
 
 
The control valve can be reset to service mode at any time by 
pressing the scroll 

 button, as such manually advancing it 

through the regeneration cycles. 
 

MANUAL REGENERATION 

 
It is possible to manually initiate a regeneration. 
1.

 

Press  the  scroll 

  button  repeatedly  until  the  display 

shows: 

 
 
 

 

If  the  control  valve  is  left  in  this  position,  the 
countdown timer will countdown to 0 sec and start a 
regeneration.
 

 

To cancel this mode, press the scroll   button before 
the countdown timer has reached 0 sec; the control 
valve will return to the service mode. 

2.

 

Press the scroll 

 button again if you want to manually 

advance the control valve to the next regeneration cycle. 

 

DRIVE MOTOR SPEED 

 
The  drive  motor  of  the  control  valve,  that  drives  the  valve 
body to its  different  regeneration positions,  will  start-up  at 
low speed to reduce its noise level. To increase the speed of 
the drive motor, simply press the scroll 

 button as soon as 

the drive motor is activated. 
 

Service Required 

 

Rgn:123 CycY:456

 

EZRFTg EZ Rot0.8 

 8:00  7 DAY REM 

Regen in 10 sec 

20:51  7 DAY REM 

Summary of Contents for pHneutralizer Series

Page 1: ... 2014 erie water treatment TM EN pHneutralizer Rev2014 06 Technical Manual WATER FILTER pH correction ...

Page 2: ...age 5 Installation Page 6 Start up Page 7 Electronic control panel Page 8 Maintenance Page 12 Hydraulic flow diagrams Page 14 Troubleshooting Page 15 Electrical wiring diagram Page 16 Default parameter settings Page 17 Exploded view System Page 18 Exploded view Timer head Page 20 Exploded view Valve body Page 22 Technical data Page 24 ...

Page 3: ...e local codes in force All plumbing and electrical connections must be done in accordance with local codes Before setting up the water filter make sure to check it for any externally visible damage do not install or use when damaged Use a hand truck to transport the water filter To prevent accident or injury do not hoist the water filter over your shoulder Do not lay the water filter on its side K...

Page 4: ...affected negatively if installed on a well verify that the well pump is powerful enough to provide sufficient flow rate for the regeneration cycle check water pressure regularly install a pressure reducer ahead of the water filter if necessary OPERATING TEMPERATURE min 4 max 38 C do not install the water filter in an environment where high ambient temperatures e g unvented boiler house or freezing...

Page 5: ... the tube 3 Place a funnel on the pressure tank opening and fill the pressure tank with the filter media make sure the riser assembly remains centered in the pressure tank 4 Rinse the pressure tank opening to remove any filter media from the threaded section 5 Unplug the top of the riser tube CONTROL VALVE 6 Make sure the O ring in the riser insert and the tank O ring around the threaded section o...

Page 6: ... water outlet of water filter treated water 1 Install the 3 valve bypass system 2 Screw the connection kit with nuts onto the in out ports on the control valve make sure to install the gasket seals Tighten the nuts firmly by hand 3 Connect the 3 valve bypass system to the adaptors on the in and out port of the control valve 4 Connect the mains water supply to the inlet of the 3 valve bypass system...

Page 7: ...2 3 minutes open a cold treated water faucet nearby the water filter and let the water run until all air is purged from the installation and the filter media is properly rinsed it is normal for the rinse water to show some discoloration let the water run until the rinse water is clear close the tap 7 Check the water filter and all hydraulic connections for leaks Calcium magnesium will be added to ...

Page 8: ...lure the display will show the message If powering off on the water filter doesn t solve this problem professional service is required SERVICE MODE In service mode the display shows the time of day and the number of days remaining until the next regeneration REGENERATION MODE In regeneration mode the display shows the remaining regeneration time and the remaining cycle time The control valve can b...

Page 9: ... scroll button again the display will show Press the up or down button to set the number of days between regenerations The regeneration cycle is necessary to prevent caking of the filter media during the service cycle which may result in an increase of pressure drop over the water filter Typically a regeneration every 7 days should be sufficient In case of high flow rates excessive water usage or ...

Page 10: ...ation Before entering the programming mode make sure that the control valve is in the service mode 1 Press the scroll button and hold it for 5 sec until the display shows 2 Within 10 sec press the up button the display will show Press the up or down button to set the length of the regeneration cycle Press the scroll button again to advance to the next regeneration cycle Cycle 1 Backwash Cycle 2 Pu...

Page 11: ...Page 11 ...

Page 12: ... minerals that dissolve in the acidic water to raise its pH to neutral level In order to maintain the optimum performance of the water filter the filter media needs to be replenished regularly Ideally the level of filter media inside the pressure tank is kept between 1 2 and 2 3 of the pressure tank height The frequency of replenishment depends on the water usage and pH of the incoming water but i...

Page 13: ...ect or contaminate your water supply However as in any device plumbed in in your water distribution system a proliferation of bacteria is possible especially in case of stagnant water Therefore this water filter will automatically rinse the filter media periodically If the power supply to the water filter is disconnected for a longer period of time we recommend when the power supply is re establis...

Page 14: ...HYDRAULIC FLOW DIAGRAMS Page 14 SERVICE BACKWASH PURGE ...

Page 15: ...ace drive motor micro switches Defective PCB Replace PCB Drain line from control valve flows continuously Water filter in regeneration Wait until regeneration finishes or manually advance regeneration to end Faulty electrical supply Verify electrical service fuse transformer Defective drive motor Replace drive motor Defective micro switch Replace micro switches Defective PCB Replace PCB Valve body...

Page 16: ...ELECTRICAL WIRING DIAGRAM Page 16 position switches power lead drive motor auxilliary contact 24V max 500mA key pad ...

Page 17: ...ge 17 Model pHneutralizer pHneutralizerXL Filter media quantity Cuft Ltr 1 28 1 5 42 1 28 1 5 42 Interval days 7 7 7 7 Cycle 1 BACKWASH min 8 8 8 8 Cycle 2 SLOW RINSE min 0 0 0 0 Cycle 3 PURGE min 2 2 2 2 Regen 0 00 0 00 0 00 0 00 ...

Page 18: ...EXPLODED VIEW SYSTEM Page 18 ...

Page 19: ... 30 mix multiple of 0 5 Cuft 3 A1000 Gravel 4 3 kg to be ordered per kg 4 38534 Riser tube assembly to be cut to length 5 28 298 11 Transformer 230 24V 50 Hz 24VA EuroT plug 6 287 166 LS Top distributor 7 2400TF JN AUX Control valve 8 568 303 1 Connection kit 1 BSP male 9 38522 Drain hose to be ordered per meter 10 38521 Clamp drain hose 2x 11 74163 Air gap with double hose barb Recommended Spare ...

Page 20: ...EXPLODED VIEW TIMER HEAD Page 20 ...

Page 21: ...or assy 2x 9 28 245 4 Cable clamp 10 71502 Strain relief power lead 11 72261 Drive motor 12 568 227 2 Worm 13 19 48 Retaining ring 14 70965 Switch cam 15 568 386 Bracket micro switches 16 568 310 Gear switch cam 17 15 184 7 Locking screw switch cam 18 15 173 12 Screw micro switches 2x 19 72451 Micro switch assy 20 71679 Cable set drive motor 21 15 102 Screw PCB 2x 22 72703 Printed Circuit Board 23...

Page 22: ...EXPLODED VIEW VALVE BODY Page 22 ...

Page 23: ... 16 568 270 4 Float valve 17 568 274 5 Injector green 18 186 118 O ring plug small 19 541 273 Plug small 20 541 254 Spring clip plug small 21 570 251 Gasket riser 22 568 334 Riser insert 23 185 214 1 O ring riser tube 24 185 337 1 O ring tank 25 541 232 Adapter ring 26 15 207 12 Screw adapter ring 2x 27 72772 Packing gland nut plastic 28 185 211 1 O ring packing gland nut 29 186 115 O ring worm dr...

Page 24: ...tralizerXL Filter media quantity Cuft Ltr 1 28 1 5 42 1 28 1 5 42 Recommended max service flow m3 hr 2 1 4 1 6 1 4 1 6 Nominal backwash flow flow to drain Ltr min 23 Rinse water usage per regeneration Ltr 227 2 continuous service flow rates higher up to x2 short period peak flow rates are possible Dimensions and weights Model pHneutralizer pHneutralizerXL Filter media quantity Cuft Ltr 1 28 1 5 42...

Page 25: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 1 a r 1 b 2 a 2 b 3 a 3 b ...

Page 26: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 4 a r 4 b 5 r 6 a r 6 b ...

Page 27: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 6 c 7 a 7 b r 7 c ...

Page 28: ... 2012 Aquion Inc PP Neutralizer Rev2014 03 r 8 ...

Page 29: ...AQUION INC Lammerdries Oost 30c B 2250 Olen Belgium 32 0 14 28 51 71 32 0 14 28 51 70 RPR RPM Turnhout BWT TVA VAT BE 0882 738 206 infobelgium eriewatertreatment com www eriewatertreatment com ...

Reviews: