Unit Description, ACCU/DCCU
16.2.2
External Interfaces
DCCU
P007833A
Figure 110
DCCU
The DCCU has the following interfaces:
•
Terminal block for four incoming DC supply cables
•
Four outgoing cables to the PSUs
Input Data
Table 123
Input data
Voltage
- (40 - 72) V DC
External fuses
4 pcs, max. 40 A
Cable diameter
4.5 - 7 mm
Conductor area
6 - 10 mm
2
Number of conductors
2
Output Data
Four cables with connectors matching the PSU DC inlet.
Table 124
Conductor area
6 mm
2
Number of conductors
2
EN/LZT 720 0008
P2A
2001-11-28
197 (485)
© Ericsson Radio Systems AB