Setup & Operation 13. UPS
72
RC620 Rev.8
■
After Windows starts up
(in normal status)
A power failure or voltage drop occurs.
The power switch is turned OFF accidentally.
→
The UPS automatically shuts down EPSON RC+ and Windows when detecting
power-off. After Windows is shut down, the ATX power output is turned off
and the LCD panel of the Controller lights.
UPS Battery
CAUTION
■
When handling the UPS battery (nickel hydride battery), observe the following
precautions for safe use.
-
Be sure to use the battery supplied as the maintenance parts from EPSON.
(Refer to Maintenance 9. Maintenance Parts List.)
-
Do not allow the positive (+) and negative (-) electrodes to short circuit.
-
Do not discard batteries into fire or heat them to high temperature.
-
Do not disassemble or alter batteries.
-
Do not apply a strong shock to the battery.
-
Stop using the battery if you see any signs of change of color or damage to the
battery.
Recycling of Battery
Dispose of the used battery appropriately in accordance with the laws and acts of your
national or local government. If you cannot dispose of a used battery properly, please
inquire of your EPSON robot supplier how to dispose of it.
Charging Battery
Turning ON the Controller will automatically charge the UPS battery.
To completely charge a discharged UPS battery, turn ON the Controller and keep it
energized for at least 2 hours after the backup operation.
Life Cycle of Battery
The battery is expendable. To maintain the Controller function, make sure to replace the
battery regularly and appropriately for the use condition.
The life cycle of the battery depends on the ambient temperature, number of backup cycles,
and backup time.
To prolong the life cycle of the battery, complete the shutdown of Windows within 2
minutes.
Relation between the life cycle of battery and the ambient temperature:
When the ambient temperature is 20 deg.C: approx. 10 years
When the ambient temperature is 25 deg.C: approx. 8 years
When the ambient temperature is 30 deg.C: approx. 5 years and 7 months
When the ambient temperature is 35 deg.C: approx. 4 years
When the ambient temperature is 40 deg.C: approx. 2 years and 9 months
Note that the life cycle above is for the reference and it does not guarantee the backup in this
period.
Also, the battery must be replaced before 10 years in any circumstances.
Summary of Contents for RC620 CU
Page 1: ...Rev 8 EM15XC3076F ROBOT CONTROLLER RC620 ...
Page 2: ...ROBOT CONTROLLER RC620 Rev 8 ...
Page 17: ...Safety This section contains information for safety of the Robot System ...
Page 18: ......
Page 24: ...8 RC620 Rev 8 ...
Page 137: ...Maintenance This section contains maintenance procedures for the Robot Controller ...
Page 138: ......