39
DB1
PV/BATT(orange)/Battery
capacity lever(four) indicator fast
flashing
DS2
:
PV/BATT(orange)indicator fast
flashing
Controller
Overheating
When heat sink of controller
exceeds 85
℃
, the controller will
automatically cut input and
output circuit. When the
temperature below 75
℃
,the
controller will resume to work.
System voltage
error
①
Check whether the battery
voltage match with the
controller working voltage.
②
Please change to a suitable
battery or reset the working
voltage.
The load is no output
DS1/DS2
:
/
Load Overload
①
Please reduce the number of
electric equipments.
②
Restart the controller.
③
wait for one night-day cycle
(night time>3 hours).
Load Short
Circuit
①
Check carefully loads
connection, clear the fault.
②
Restart the controller.
③
wait for one night-day cycle
(night time>3 hours).
Inverter fault
Inverter fault
Fault code
LCD
Indicator
Output short circuit
E001
Fault icon blink (1S)
Load indicator blink
Output overload
E002
Output voltage abnormal
E003
Input over voltage
E005
Input low voltage
E006
Input over current
E007
Overheating
E008
Communication timeout
E099
NOTE:
With combination of the RCM and DS1/DS2 modules, the information
of the inverter (to be supplied by our company) can be displayed by the
DS1/DS2 module.
Load and fault icon blink
Summary of Contents for TRIRON N Series
Page 2: ......
Page 4: ......
Page 12: ...6 1 4 Designations of Controller Models EXAMPLE...
Page 14: ...8...
Page 22: ...16 3 Install the modules...
Page 23: ...17...
Page 55: ...49 Annex II Dimensions TRIRON1206N TRIRON1210N Unit mm...
Page 56: ...50 TRIRON2206N TRIRON2210N Unit mm...
Page 57: ...51 TRIRON3210N Unit mm...
Page 58: ...52 TRIRON4210N TRIRON4215N Unit mm Any changes without prior notice Version number 1 2...
Page 59: ......