Annex 4: Factory settings
No.
1
2
3
4
5
6
7
8
9
10
14
15
16
17
18
19
20
21
22
23
24-
37
38
39
40
41
42
43
Parameter
LANGUAGE
CONTROL-MODE
I CONVERTER PRIM.
I CONVERTER SEC.
END STOP
CONTROL SERIE
CONTROL PRINCIPLE
POWER 1st STAGE
TARGET COS-PHI
TARGET 2nd COS-PHI
MEASURING VOLTAGE
V-CONVERTER
FREQUENCY
CONNECTING TIME
DISCONNECT. TIME
DISCHARGE TIME
ALARM TEMPERATURE
FAN TEMPERATURE
MESSAGE RELAY
EXT. INPUT
Values 2nd parameter set
HARMONICS THD-V
HARMONICS THD-I
CLOCK / DATE
Q-OFFSET
CONTRAST
BASIC SETTINGS
Default setting
ENGLISH
[1] 3x5 single-phase
capacitors L-N
1000 A
5 A
3 x 5
1
INTELLIGENT
25.00 kvar
0.98 IND
- SUPPLY -
L-L 400 V (L-N 230V)
- NO -
40...90 Hz
40 sec.
40 sec.
60 sec.
55°C
30°C
- OFF -
- NO -
7 %
--,--
- NO -
4
- NO -
Programmed values of this
system (to be entered by
manufacturer or operator)
Default values are the same
as in the 1st parameter set.
Note: The following values for the default settings apply only if the controller is supplied
directly from the manufacturer. Otherwise, these values may have been replaced by
settings made by the manufacturer of the compensation system (optimal values for the
relevant network)
- 37 -