Section 3: CONNECTION ALTERNATIVES MEASURING VOLTAGE
AND MEASURING CURRENT
According to the existing grid and the desired operating mode (CONTROL-MODE
Programming) the BR7000 has to be connected accord. one of the following alternatives.
In grids without neutral conductor the connector N from meas.voltage at the
controller has to be open.
Program the ExpertMode 1 as: 13 U-connection: -- L1 - L2 - L3
Alternative 1: measuring performed in each phase - 3 current transformers needed
Use: CONTROL-MODE: 1 - 4
BR7000
Alternative 2: single-phase measuring via current transformer in L1 Values extrapolated (balance assumed).
Measuring complies with conventional measuring for switching of three-phase capacitors.
Use: CONTROL-MODE 5
BR7000
Alternative 3: single-phase measuring as alternative 2 , but with capacitor current measuring in the compensation
system for collection of real capacitor currents.
Use: CONTROL-MODE 6
BR7000