66
Error Message
Possible cause
Fault elimination
Error
Error text
237
ANALOG
INPUT
This alarm occurs when the A/D
conversion of the analog inputs returns
frozen values, on all the converted
signals, for more than 400 ms. The goal of
this diagnosis is to detect a failure in the
A/D converter or a problem in the code
flow that skips the refresh of the analog
signal conversion.
If the problem occurs permanently
it is necessary to replace the logic
board.
238
HW FAULT
EV.
At start-up, the hardware circuit dedicated
to enable and disable the EV drivers is
found to be faulty. The hexadecimal value
“XX” facilitates EP technicians debugging
the problem.
This type of fault is not related to
external components. Replace the
logic board.
239
CONTROL
LER MISM.
The software is not compatible with the
hardware. Each controller produced is
“signed” at the end of line test with a
specific code mark saved in EEPROM
according to the customized part number.
According with this “sign”, only the
customized firmware can be uploaded.
1- Upload the correct firmware.
2- Ask for assistance to a EP
technician in order to verify that
the firmware
is correct.
240
EVP
DRIVER
OPEN
The EVP driver is not able to drive the
EVP coil. The device itself or its driving
circuit is damaged.
This fault is not related to external
components. Replace the logic
board.